background image

 

PM

-

2133D User’s Manual v1.00  

 

  Last Revised: Feb. 2020                       Page: 27   

Copyright © ICP DAS Co., Ltd.    All Rights Reserved.  

www.icpdas.com

      

 E-mail: [email protected]

 

    Modbus Module #4 

  Input Register :Power value (Float) 

Parameter 

name 

Modbus Register 

Len 

Data Type 

Range 

Units 

Comment 

Modicom Format 

Hex 

V_a 

34353-34354 

0x1100-0x1101 

DWord 

Float 

 

Volt 

 

I_a 

34355-34356 

0x1102-0x1103 

DWord 

Float 

 

Amp 

 

kW_a 

34357-34358 

0x1104-0x1105 

DWord 

Float 

 

kW 

 

kvar_a 

34359-34360 

0x1106-0x1107 

DWord 

Float 

 

kvar 

 

kVA_a 

34361-34362 

0x1108-0x1109 

DWord 

Float 

 

kVA 

 

PF_a 

34363-34364 

0x110A-0x110B 

DWord 

Float 

 

 

 

kWh_a 

34365-34366 

0x110C-0x110D 

DWord 

Float 

 

 

 

kvarh_a 

34367-34368 

0x110E-0x110F 

DWord 

Float 

 

 

 

kVAh_a 

34369-34370 

0x1110-0x1111 

DWord 

Float 

 

 

 

V_b 

34371-34372 

0x1112-0x1113 

DWord 

Float 

 

Volt 

 

I_b 

34373-34374 

0x1114-0x1115 

DWord 

Float 

 

Amp 

 

kW_b 

34375-34376 

0x1116-0x1117 

DWord 

Float 

 

kW 

 

kvar_b 

34377-34378 

0x1118-0x1119 

DWord 

Float 

 

kvar 

 

kVA_b 

34379-34380 

0x111A-0x111B 

DWord 

Float 

 

kVA 

 

PF_b 

34381-34382 

0x111C-0x111D 

DWord 

Float 

 

 

 

kWh_b 

34383-34384 

0x111E-0x111F 

DWord 

Float 

 

 

 

kvarh_b 

34385-34386 

0x1120-0x1121 

DWord 

Float 

 

 

 

kVAh_b 

34387-34388 

0x1122-0x1123 

DWord 

Float 

 

 

 

V_c 

34389-34390 

0x1124-0x1125 

DWord 

Float 

 

Volt 

 

I_c 

34391-34392 

0x1126-0x1127 

DWord 

Float 

 

Amp 

 

kW_c 

34393-34394 

0x1128-0x1129 

DWord 

Float 

 

kW 

 

kvar_c 

34395-34396 

0x112A-0x112B 

DWord 

Float 

 

kvar 

 

kVA_c 

34397-34398 

0x112C-0x112D 

DWord 

Float 

 

kVA 

 

PF_c 

34399-34400 

0x112E-0x112F 

DWord 

Float 

 

 

 

kWh_c 

34401-34402 

0x1130-0x1131 

DWord 

Float 

 

 

 

kvarh_c 

34403-34404 

0x1132-0x1133 

DWord 

Float 

 

 

 

kVAh_c 

34405-34406 

0x1134-0x1135 

DWord 

Float 

 

 

 

V_avg 

34407-34408 

0x1136-0x1137 

DWord 

Float 

 

Volt 

 

I_avg 

34409-34410 

0x1138-0x1139 

DWord 

Float 

 

Amp 

 

kW_tot 

34411-34412 

0x113A-0x113B 

DWord 

Float 

 

kW 

 

kvar_tot 

34413-34414 

0x113C-0x113D 

DWord 

Float 

 

kvar 

 

kVA_tot 

34415-34416 

0x113E-0x113F 

DWord 

Float 

 

kVA 

 

Содержание PM-2133D Series

Страница 1: ...PM 2133D User s Manual v1 00 Last Revised Feb 2020 Page 1 Copyright ICP DAS Co Ltd All Rights Reserved www icpdas com E mail service icpdas com...

Страница 2: ...pter 3 Installation 8 3 1 Inspection 8 3 2 Safety 8 3 2 1 Dimension and Latch 8 3 2 2 Mounting and Dismounting 10 3 2 3 CT s installation steps 12 Chapter 4 Wiring Diagrams 13 4 1 Connection 13 4 2 Wi...

Страница 3: ...y consumption readings from the monitored equipments in real time under operation These compact size and cost effective power meters are equipped with revolutionary wired clip on CT various types supp...

Страница 4: ...resulting from the use of this product ICP DAS reserves the right to change this manual at any time without notice The information furnished by ICP DAS is believed to be accurate and reliable However...

Страница 5: ...l Rights Reserved www icpdas com E mail service icpdas com 1 4 1 Limitation of Warranty This warranty does not apply to defects resulting from unauthorized modification misuse or use for reason other...

Страница 6: ...6 mm 0 3 A 400 A Measurement Frequency 50 Hz Range 45 55 Hz 60 Hz Range 55 65 Hz W Accuracy Better than 0 5 PF 1 Power Parameter Measurement True RMS voltage Vrms True RMS current Irms Active Power kW...

Страница 7: ...t ICP DAS Co Ltd All Rights Reserved www icpdas com E mail service icpdas com Aux Power Input Range 85 264 VAC 277 VAC available Power Consumption 6 W Dimensions W x L x H 110 mm x 50 mm x 115 mm Envi...

Страница 8: ...r extreme conditions d Damage during shipment 3 2 Safety Please use the soft dry clothes to clean the instrument Please do not use any chemical or detergent or volatile solvents to clean the instrumen...

Страница 9: ...Wire Disconnection 1 Open the CT clip to detach the CT do not remove the CT terminal lines if possible Note if you need to remove the terminal lines always detach the CT before removing the CT termina...

Страница 10: ...o Ltd All Rights Reserved www icpdas com E mail service icpdas com 3 2 2 Mounting 1 Prepare a panel and cut a hole to the specified size unit mm 2 Remove the latch assembly i Press the protruding pin...

Страница 11: ...eserved www icpdas com E mail service icpdas com The protruding pin The protruding pin Keep on pressing the protruding pin to slide the latch assembly to the groove The groove 3 Attach the PM 2133D to...

Страница 12: ...Ltd All Rights Reserved www icpdas com E mail service icpdas com 3 2 3 CT s installation steps At the bottom of the CT there is a K L mark Open the CT clip Make sure the power current direction follo...

Страница 13: ...black white black white black wire sequences CT1 K CT1 L CT2 K CT2 L CT3 K CT3 L Then connect the CT s and close the CT clip Make sure the arrow direction sign on CT s follows current flow direction...

Страница 14: ...e each set of smart meter PM 2133D series and its attached split type clip on CT are calibrated set by set The mix use may cause wrong measurements 4 To install CT s correctly please ensure the CT lin...

Страница 15: ...33D User s Manual v1 00 Last Revised Feb 2020 Page 15 Copyright ICP DAS Co Ltd All Rights Reserved www icpdas com E mail service icpdas com 4 2 Wiring 1P2W 1CT PM 2133D 1P3W 2CT PM 2133D 3P3W 2CT PM 2...

Страница 16: ...PM 2133D User s Manual v1 00 Last Revised Feb 2020 Page 16 Copyright ICP DAS Co Ltd All Rights Reserved www icpdas com E mail service icpdas com 3P3W 3CT PM 2133D 3P4W 3CT PM 2133D...

Страница 17: ...data which are currently shown on the 8 Digit LED Display and the status of RS 485 communication Tx Rx PM 21333D also has a built in four buttons of keypad which is used to adjust the power data which...

Страница 18: ...n also change the setting of the power meter The following sections describe the features provided 5 2 1 Normal Mode After power up PM 2133D the default power data shown is power data of I_a Phase A C...

Страница 19: ...E mail service icpdas com 5 2 2 Setup Mode User can press the buttons of Keypad to enter the Setup Mode to adjust the parameters setting of PM 2133D The steps are as below i Press the Enter button to...

Страница 20: ...for selection Modbus Data Format setting Press the Enter button the current Data Format setting will blink Press the button and button to adjust the Data Format setting There are 6 options 8N1 8 data...

Страница 21: ...digit press the Enter button the hundreds digit of the CT ratio will blink Press the button and button to adjust the setting of hundreds digit After completing the setting of hundreds digit press the...

Страница 22: ...020 Page 22 Copyright ICP DAS Co Ltd All Rights Reserved www icpdas com E mail service icpdas com iv Repeat Step ii iii to complete all parameter settings v After all parameter settings are completed...

Страница 23: ...st significant bit sent first None Parity Odd Parity or Even Parity 1 stop bits or 2 stop bits Error Check Cyclical Redundancy Check CRC Baud Rate 9600 19200 Default 38400 115200 Modbus slave address...

Страница 24: ...Lo Byte SEEE EEEE EMMM MMMM MMMM MMMM MMMM MMMM Value 1 S x 1 M x 2E 127 0 E 255 S represents the sign bit where 1 is negative and 0 is positive E is the two s complement exponent with an offset of 12...

Страница 25: ...UInt 1 1P2W 2 1P3W 3 3P3W2CT 4 3P3W3CT 5 3P4W3CT 5 Set Energy to Zero 44108 0x100B Word UInt 0x0055 Only Write Reset to Factory Settings 44109 0x100C Word UInt 0x0055 Only Write Default Frequency 4411...

Страница 26: ...gister Len Data Type Range Default value Units Comment Modicom Format Hex Wiring Type 30513 0x0200 Word UInt 9 1P2W 10 1P3W 11 3P3W2CT 12 3P3W3CT 13 3P4W 13 Phase Sequence 30514 0x0201 Word UInt 0 Neg...

Страница 27: ...kW_b 34375 34376 0x1116 0x1117 DWord Float kW kvar_b 34377 34378 0x1118 0x1119 DWord Float kvar kVA_b 34379 34380 0x111A 0x111B DWord Float kVA PF_b 34381 34382 0x111C 0x111D DWord Float kWh_b 34383...

Страница 28: ...0 1A kW_a 34613 34614 0x1204 0x1205 DWord Int32 0 1kW kvar_a 34615 34616 0x1206 0x1207 DWord Int32 0 1kvar kVA_a 34617 34618 0x1208 0x1209 DWord Int32 0 1kVA PF_a 34619 0x120A Word Int 0 1000 0 001PF...

Страница 29: ...74 0x1240 0x1241 DWord Int32 0 99999999 0 1kvarh 0 9999999 9 kVAh_tot 34675 34676 0x1242 0x1243 DWord Int32 0 99999999 0 1kVAh 0 9999999 9 Freq_a 34677 0x1244 Word Int 45 65 1Hz 45 65 Freq_b 34678 0x1...

Страница 30: ...32C Word Int 0 1000 0 001PF 0 1 000 kWh_c 34910 34911 0x132D 0x132E DWord Int32 0 99999999 0 1kWh 0 9999999 9 kvarh_c 34912 34913 0x132F 0x1330 DWord Int32 0 99999999 0 1kvarh 0 9999999 9 kVAh_c 34914...

Страница 31: ...ng equipments before the CT lines detach from the terminals of the smart meter Otherwise it will cause the severe injury Q3 If the turn point of the split type clip on CT has broken or inner Ferrite c...

Страница 32: ...RS 485 master have to provide the bias for PM 2133D series Otherwise the tM SG4 or SG 785 should be added to provide the bias All ICP DAS controllers and converters provide the bias Q7 What the power...

Страница 33: ...A If the target is more than 400A we suggest the solution as follow For example the target is to measure maximum 800A current We can measure big CT output and set a CT Ratio Note A Primary CT accuracy...

Страница 34: ...a current of 200A becomes 5A Since the meter sees 5A many of the measurements it reports will be low by a factor of 40 unless they are scaled up by 40 Current transformer CT Ratio PM 2133DP Current t...

Страница 35: ...wye connected system line to line voltages will be the voltages between the terminals A B B C A C On a three phase wye connected system line to ground voltages will be the voltages between the termina...

Страница 36: ...ired to set different Display Voltage value If the voltage is not displayed as expected value please refer to the table below and check if the setting value is set accurately Line to Ground Voltage Li...

Страница 37: ...on the supply voltage available at your facility Example PRI Voltage 720V SEC Voltage 120V Check the connection diagram three phase Y and delta phase sequence to ensure compatibility Adding potential...

Страница 38: ...nt serial ports to share slave devices Modbus mode can be used to convert the Modbus RTU ASCII protocols while raw data mode can be used for DCON or other query response protocols Different baud rates...

Страница 39: ...mm 2 Quantity Diameter mm Flat cable 1 6 3 2 15 10 PM 2133D 100 P 10mm 60A 2 0 3 6 20 Twisted pair 2 0 7 0 6 3 4 17 3 5 7 0 8 4 0 20 5 5 7 1 0 5 0 30 8 0 7 1 2 6 0 40 14 7 1 6 7 6 55 22 7 2 0 9 2 70 1...

Отзывы: