Prepare for device:
DN-37 (optional) wiring terminal board.
Exterior power supply device. For example: DP-665 (optional)
Self-test wiring as follows:
1.
Use the DN-37 to connect the CON1 on board.
2.
Connect the
COM(0-7)
with
DIA(0-7)
.
(Pin2/5/8/21/24/26/28/11
connects to
Pin12/13/14/15/16/17/18/19).
3.
Power Supply GND
connects to
DIB0…DIB7 (Pin30/31/32/33/34/35/36/37)
.
Power Supply GND
connects to
GND (Pin29)
.
4.
Power Supply (+24 V)
connects to
NO(0-7) (Pin1/4/7/20/23/25/27/10)
.
Self-Test