Ethernet I/O Modules
ICP DAS CO., LTD.
PETL/tET/tPET DIO Series User Manual, Ver. 2.2, Aug. 2017, Page: 56
DI/DO Configuration
The following table provides an overview of the parameters contained in the
DI/DO Configuration
section:
Item
Description
Digital Output
Host/Slave Watchdog
Timeout
This parameter is used to configure the Host Watchdog timeout value. If there
is no Modbus TCP communication activity for the specified period (the
timeout), then the Host Watchdog will activate an alarm.
Enable Safe Value
(Enable Watchdog)
This parameter is used to enable the watchdog on each DO channels.
Safe Value
This parameter is used to define the DO safe value for the PETL/tET/tPET
module. If the Host Watchdog alarm is activated, the DO will be set to the
user-defined safe value.
Power-On Value
This parameter is used to define the DO Power-on value. On boot up, the DO is
set to the user-defined Power-on value.