![ICP DAS USA I-8014W Скачать руководство пользователя страница 71](http://html1.mh-extra.com/html/icp-das-usa/i-8014w/i-8014w_user-manual_3653750071.webp)
I-8014W API User Manual, v1.0.1, June 2011
Copyright © 2011 ICP DAS Co., Ltd. All Rights Reserved. E-mail: [email protected]
71
Parameter
slot: 0 ~ 7
chArr[]: an array for setting the channel to scan. The channel indices define the
scan order; the maximum channel number is 16.
gainArr[]: an array for setting the input type for the corresponding channel with
the same index in chArr[].
0:
+/-10 V,
1:
+/-5 V,
2:
+/-2.5 V,
3:
+/-1.25 V,
4:
+/-20 mA
scanChCount: the count of channels which are added in chArr[]
sampleRate: total sampling rate
,
2 ~ 250 kHz
scanMode:
1
: standard mode
2
: virtual sample and hold mode
triggerSource:
0
: software trigger
1
: internal hardware trigger
2
: external hardware trigger
triggerState:
0
: rising edge trigger, it is valid only for external hardware trigger.
1
: falling edge trigger, it is valid only for external hardware trigger.
*
realSampleRate:
[Output]
the real sampling rate that the I-8014W used
Return
None