I-7530A-MR Modbus RTU to CAN
Converter User’s Manual (Version 1.08, 07/2019) ------------- 75
4. Change CAN bus baud rate
This command is used to Change CAN bus baud rate. After successfully
setting, the module will response a successful setting message, and then
reboots.
Request command:
Field Name
Size
Value Range
Example
Hex rule
Node ID
1 byte
0x01~0xF7
0x01
Function Code
1 byte
0x10
0x10
Start Address
2 bytes
0x0100
0x0100
Word Count
2 bytes
0x0002
0x0002
Byte Count
1 byte
0x04
0x04
Data-1
2 bytes
0x0004 (Note1)
0x0004
Data-2
2 bytes
0x0000~0x0008,
0x000F (Note2)
0x0008
(1000kbps)
Note1: This value is command field.
Note2: This value is baud rate of CAN bus.
B
Description
0x0000
10 kbps baud rate of CAN
0x0001
20 kbps baud rate of CAN
0x0002
50 kbps baud rate of CAN
0x0003
100 kbps baud rate of CAN
0x0004
125 kbps baud rate of CAN
0x0005
250 kbps baud rate of CAN
0x0006
500 kbps baud rate of CAN
0x0007
800 kbps baud rate of CAN
0x0008
1000 kbps baud rate of CAN
0x000F
User-defined baud rate of CAN