3.I-7530A-MR-FD Parameter Configuration
Before starting the I-7530A-MR-FD converter tests, users need to
configure the RS-232/485/422, Modbus and CAN parameters via the
UART2CAN Utility tool. The details of this procedure are shown below.
Step1:
Turn off the DC power connected with these two
I-7530A-MR
–FD modules.
Step2:
Set the Init/Normal switches on the back of the
I-7530A-MR-FD
_A to the “Normal” position. Then, turn on the DC power.
Afterwards, set the Init/Normal switches to the “Init” position and hold it
at least 3 seconds. The CAN LED and UART LED of the
I-7530A-MR-FD_A will flash approximately once per second. That
means that the I7530A-MR-FD is working in the configuration mode.
Step3:
Run the UART2CAN Utility. The “UART2CAN Utility.exe” is
located on the product CD-ROM or is downloaded from the web site:
https://www.icpdas.com/en/product/I-7530A-MR-FD
Download Center-> Utility &Tool->Utility
Step4:
Select the proper PC COM port No., baud rate and data format,
which are used to be communicated with the I-7530A-MR-FD_A. When
the Utility starts, the following dialog will be popped up. The default
setting of the PC COM port field is configured at 115200bps, 8 Data Bits,
1 Stop bit, and no parity.