2.4 Terminator Resistor Settings
According to the ISO 11898 specifications, the CAN Bus network
must be terminated by two terminal resistors (120
Ω
). They are shown as
following figure.
Figure 2-8
:
Terminal Resistor
Therefore, the I-7530A-MR-FD module supplies a jumper for
activating the terminal resistor. If users want to use this terminal resistor,
please open the I-7530A-MR-FD cover and use the JP3 to activate the
120
Ω
terminal resistor built in the module, as the Figure 2-9. Note that the
default setting is active.
Figure 2-9
:
Terminal Resistor Jumper