I-7080, I-7080D, I-7080B, I7080BD User Manual (V 2.2) ------------------ 61
2.37 @AADI
Description
: Read the status of D/O & alarm. Refer to Sec.
2.8 for more information.
Syntax
: @AADI[chk](cr)
@ is a delimiter character
AA=2-character HEX module address, from 00 to FF
[chk]=2-character checksum, if checksum disable
no [chk]
(cr)=0x0D
Response
: valid command
!AAS0D00[chk](cr)
invalid command
?AA[chk](cr)
no response
syntax error or communication
error or address error
! is a delimiter character indicating a valid command
? is a delimiter character indicating a invalid command
AA=2-character HEX module address
D=0
D/O0=D/O1=OFF
=1
D/O0=ON, D/O1=OFF
=2
D/O0=OFF, D/O1=ON
=3
D/O0=D/O1=ON
S=0
counter 0 alarm=disable, counter 1 alarm=disable
=1
counter 0 alarm=enable, counter 1 alarm=disable
=2
counter 0 alarm=disable, counter 1 alarm=enable
=3
counter 0 alarm=enable, counter 1 alarm=enable
S=0
counter 0 alarm=disable
=1
counter 0 alarm=enable & MOMENTARY mode
=2
counter 0 alarm=enable & LATCH mode
[chk]=2-character checksum, if checksum disable
no [chk]
(cr)=0x0D
Example
:
command: @01DI(cr)
response : !0100000(cr)
command: @02DI(cr)
response : !0230100(cr)
Alarm disable.
D/O0=D/O1=OFF
Alarm enable. D/O0=ON.
D/O1=OFF
7080/7080D
Alarm
mode 0
Alarm
mode 1