I-7055D 8 Channel Isolated DI (Counter)and 8 Channel Isolated DO DAQ Module
- QuickStart (Feb/2016)
ICP DAS USA, Inc.
| 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717
3
4. Default Settings
。
Module Address: 01
。
DIO Type: Type 40
。
Baud Rate: 9600 bps
。
Checksum disabled
。
J3 set to INIT mode enabled
5. Configuration
To install the module, follow the steps below:
1. Connect the digital input and output.
2. Connect the module to the RS-485 network using the DATA+ and DATA- terminals. If
the host is only equipped with an RS-232 interface, then an RS-232 to RS-485
converter will be required.