3
Q1: Could you please confirm that GW-7472 works with SLC-500 (SLC5/05) without any
problems?
A1: We never test GW-7472 this device with SLC-500. But this device ever tested with the Hilscher
CIFX 50-RE Ethernet/IP master. It can communicate with the master via following I/O connection
methods.
(1) Transport and trigger: Exclusive-Owner, Cyclic
(2) Original to Target Type: POINT2POINT, (MULTICAST not supported)
(3) Target to Original Type: POINT2POINT, MULTICAST
Q2: In some case, the byte order of the AI/AO word data in the communication is reversed, i.e.
low byte is MSB and high byte is LSB. Is there a byte swapping function?
A2: After the firmware version 1.5 of GW-
7472, the utility supports the “Byte Order Setting” as shown
in the following figure.