background image

 

GW-7228 Quick Start v1.2 2011/05 

6

6

6

6/

/

/

/8

8

8

8

 

 

Figure 9: J1939 configuration screen 

  Upload Parameter to the GW-7228 

 

After the previous parameter settings, users need to upload the parameters to 

the GW-7228.  

 

Figure 10: Parameter upload screen 

   Modbus Communication 

 

Set J1939 output data  

 

Using the Modbus command as below: 
 FC16 Write multiple registers (4xxxx) for AO 

 

Example:  
In the address 40001, write the value in 0x1234. 
[Request Command] (Byte0, Byte1... Byten) (Hex) 
01 10 00 00 00 01 02 

12 34

 

AB 27(CRC)

 

 
 

Byte 

Order In 

Modbus 

Data 

Length 

PGN 

 (DEC)  

Priority 

ECU’s 

J1939 

Address 

ECU’s 

J1939 

Address 

Transm-

ission 

Repetiti-

on 

Byte Order  

In J1939 

Data Field 

Содержание GW-7228

Страница 1: ...local distributors for more information Save the shipping materials and cartons in case you want to ship in the future Appearance and pin assignments CAN DB9 Male Connector Pin Description 1 Not Conne...

Страница 2: ...r 100 ms No Error Always turned on CAN Bus Transmission Fail Blink per 100 ms CAN Bus Off Blink per 500 ms Can t Claim Address in J1939 Network Blink per 1000 ms PWR LED Power Failure Off Transmission...

Страница 3: ...orts with the GW 7228 modules and ECU e g engine in J1939 network using the following structure as Figure 3 Figure 3 CAN bus Wire Connection Step3 Modbus network Serial port connection It is recommend...

Страница 4: ...the controller must be set the same serial communication parameters of the Modbus network configuration The Modbus network configuration screen from GW 7228 is shown as Figure 6 Figure 6 Modbus confi...

Страница 5: ...g table shows the current planning Figure 8 Example of a parameter group definition of SAE J1939 71 Table 1 Configuration data of J1939 and Modbus Parameters PGN Data Length bytes Byte Order In J1939...

Страница 6: ...rameter upload screen Modbus Communication Set J1939 output data Using the Modbus command as below FC16 Write multiple registers 4xxxx for AO Example In the address 40001 write the value in 0x1234 Req...

Страница 7: ...B4 47 CRC Start or Stop sending J1939 output message 1 Using the Modbus command as below FC6 Write single register 4xxxx for AO Example Start sending J1939 output message In the address 42009 write th...

Страница 8: ...t message table is not zero 5 How to restore factory default 1 Power on the GW 7228 2 Change the Dip Switch position of the GW 7228 and to complete the following steps in 5 seconds Step1 From Normal t...

Отзывы: