GW-5492/GW-5493 User’s Manual
V1.01 2011/09/01
20
Figure 15. BACnet basic information
Port: BACnet Port. Default port is 47808 (0xBAC0)
ID: Device_Identifier property, range from 0 to 4194302
Name: The device name showed on BACnet network.
Retry: Number_Of_APDU_Retries property
Timeout: APDU_Timeout property
UTC_Offset: The time offset from Coordinated Universal Time
Location: Location property
Description: Object_ Description property
3.7.2
BACnet Object Types and instance settings
The BACnet Gateway supports 10 types of standard BACnet Objects including Analog Input,
Analog Output, Analog Value, Binary Input, Binary Output, Binary Value, Multistate Input, Multistate
Output, Multistate Value and Device. Figure 15 shows the 9 types of BACnet Objects, the 3-column
sub fame consisting of Type, Maximum, and Instance number.