B-3. DL-110S-E Modbus Address Mappings (Base 1) Version 1.2.0 Jun 2023
- 68 -
Address Description
Attribute
40886
Starting second when logging in period mode, 0 ~
59
R/W
40887
Ending year when logging in period mode, 2000 ~
2159
R/W
40888
Ending month when logging in period mode, 1 ~
12
R/W
40889
Ending date when logging in period mode, 1 ~ 31 R/W
40890
Ending hour when logging in period mode, 0 ~ 23 R/W
40891
Ending minute when logging in period mode, 0 ~
59
R/W
40892
Ending second when logging in period mode, 0 ~
59
R/W
00227
Write 1 to reload default TCP settings and reboot
module
Only for Modbus TCP protocol
W
00234
Write 1 to reboot module
Only for Modbus TCP protocol
W
00257
RS-485 Protocol, 0: DCON, 1: Modbus RTU
Only for Modbus RTU protocol
R/W
00261
RS-485 host watchdog mode, 1: enable, 0:
disable.
Only for Modbus RTU protocol
R/W
00270
Host watch dog timeout status, write 1 to clear
host watch dog timeout status
Only for Modbus RTU protocol
R/W
00273
Reset status, 1: first read after powered on, 0: not
the first read after powered on
Only for Modbus RTU protocol
R
00280
Write 1 to clear all high latched analog input
values
W
00281
Write 1 to clear all low latched analog input values W
00385 ~
00391
Write 1 to clear high latched analog input value of
channel 0 to 6
W
00417 ~
00423
Write 1 to clear low latched analog input value of
channel 0 to 6
W