DL-100S-E / DL-101S-E / DL-110-E / DL-120-E User Manual Version 1.0.0 May 2020
- 61 -
B-2. DL-101S-E Modbus Address Mappings (Base 1)
Address Description
Attribute
30001 ~
30005
40001 ~
40005
Analog input value of channel 0 to 4. channel 0:
relative humidity in 0.01%, channel 1:
temperature in 0.01°C, channel 2:temperature in
0.01°F, channel 3: dew point temperature in
0.01°C, channel 4: dew point temperature in
0.01°F
R
40181 ~
40196
Module alias name
R
40225 ~
40229
High alarm limit of channel 0 to 4, channel 0:
relative humidity in 0.01%, channel 1:
temperature in 0.01°C, channel 2:temperature in
0.01°F, channel 3: dew point temperature in
0.01°C, channel 4: dew point temperature in
0.01°F
R/W
40233 ~
40237
Low alarm limit of channel 0 to 4, channel 0:
relative humidity in 0.01%, channel 1:
temperature in 0.01°C, channel 2:temperature in
0.01°F, channel 3: dew point temperature in
0.01°C, channel 4: dew point temperature in
0.01°F
R/W
40272
Modbus NetID
R/W
30301
40301
Number of the digital input channels
R
30311
40311
Number of the digital output channels
R
30321
40321
Number of the analog input channels
R
30331
40331
Number of the analog output channels
R
30352
40352
Firmware version in hex format
R
40449
Relative humidity offset in 0.01%
R/W
40450
Temperature offset in 0.01°C
R/W
40481
Firmware version (low word)
R
40482
Firmware version (high word)
R
40483
Module name (low word), 0x0100
R
40484
Module name (high word), 0x444C
R