CAN-2057D 

User’s Manual (v1.10, April/2015) 

2.3  LED Description 

PWR LED 

The  CAN-2057D  needs  the  power  of  10  ~  30  V

DC

.  Under  a 

normal  connection,  a  good  power  supply  and  a  correct  voltage 

selection, as the unit is turned on, the LED will light up in red. 

 

NET LED 

The  NET  LED  indicates  the  current  status  of  the  DeviceNet 

communication link. 

condition 

status 

indicates 

Init Off 

Off line 

Device is not online 

Off 

Connection timeout 

I/O connection timeout 

Flashing 

On line 

Device is on line, but not 

communicating 

Init solid 

Link failed 

(Critical) Device has detected an 

error that has rendered it incapable 

of communicating on the link; for 

example, detected a duplicate node 

address or network configuration 

error 

Solid 

On line, communicating  Device is online and communicating 

   

 

MOD LED 

This LED provides the devices status. It indicates whether or not 

the device is operating properly. 

condition 

status 

indicates 

Off 

Normal 

 

Solid 

Critical fault 

Device has unrecoverable fault.   

Flashing  Non_critical fault 

Device has recoverable fault to 

recover. If users want to fix the 

problem, reconfiguring 

device’s 

MAC ID or resetting device may 

work.

 

 

 

 

Содержание CAN-2057D

Страница 1: ...ted in one year from the date of delivery to customers Warning ICP DAS revises the manual at any time without notice However no responsibility is taken by ICP DAS unless infringement act imperils to p...

Страница 2: ...e 6 2 2 Node ID Baud Rate Rotary Switch 7 2 3 LED Description 8 2 4 PIN Assignment 10 2 5 Wire Connection 11 3 DeviceNet Profile Area 12 3 1 DeviceNet Statement of Compliance 12 3 2 Identity Object Cl...

Страница 3: ...mote data acquisition environmental monitoring and packaging machines control etc The CAN 2057D follows DeviceNet specification Volume I II Release 2 0 User can access the digital output status and se...

Страница 4: ...le Isolation Field to Logic 3750 Vrms ESD Protection 4 kV Contact for each channel Others DeviceNet Status 3 LEDs for PWR NET MOD Terminal Resister 1 LED as terminator resister indicators DO LED 16 LE...

Страница 5: ...roup 2 Only Server non UCMM capable Support Predefined Master Slave Connection Set Connection supported 1 connection for Explicit Messaging 1 connection for Polled I O 1 connection for Bit Strobe I O...

Страница 6: ...CAN 2057D User s Manual v1 10 April 2015 6 2 Hardware 2 1 Structure Top View Bottom View...

Страница 7: ...are for the tens digit and the units digit of the node ID The node ID value of this demo picture is 32 The rotary switch for baud rate handles the CAN baud rate of CAN 2057D module The relationship be...

Страница 8: ...e Device is on line but not communicating Init solid Link failed Critical Device has detected an error that has rendered it incapable of communicating on the link for example detected a duplicate node...

Страница 9: ...ual v1 10 April 2015 9 Terminal Resistor LED When enable the 120 terminator resistor the LED will turn on DO LED If the DO LED turns on it means that the corresponding DO channel sends an ON voltage l...

Страница 10: ...CAN 2057D User s Manual v1 10 April 2015 10 2 4 PIN Assignment...

Страница 11: ...CAN 2057D User s Manual v1 10 April 2015 11 2 5 Wire Connection...

Страница 12: ...Device Information Description Version Description of DeviceNet Specification Volume I Release 2 0 Volume II Release 2 0 Vendor Name ICP DAS Device Profile Name CAN 2057D Production Revision 1 1 Devic...

Страница 13: ..._Single Yes Instance Attribute Instance ID 1 Attribute ID Description Method DeviceNet Data Type Value 1 Vendor Get UINT 803 2 Product type Get UINT 0x00 3 Product code Get UINT 0x200 4 Major Minor of...

Страница 14: ...et within slave devices The default IO connection path is as follow Connection Path Class ID Instance ID Attribute ID Poll Produced 0x04 0x64 0x03 Poll Consumed 0x04 0x64 0x03 Bit Strobe Produced 0x04...

Страница 15: ...network s point of view An input will produce data on the network and an output will consume data from the network Class attribute Instance ID 0 Attribute ID Attribute name Data Type Method Value 0x01...

Страница 16: ...hannel 0 DO value Bit 1 channel 1 DO value Bit 15 channel 15 DO value Note x is channel number of module Instance attribute Instance ID 0x64 Attribute ID Description Method DeviceNet Data Type Value 0...

Страница 17: ...ute_Single and Set_ Attribute_Single to read and write CAN 2057D module Application Object1 defines digital output channels configuration Class attribute Instance ID 0 Attribute ID Attribute name Data...

Страница 18: ...hannel 0 DO safe value mask Bit 1 channel 1 DO safe value mask Bit 15 channel 15 DO safe value mask Bit value 1 apply safe value setting Bit value 0 apply DO output value 0x04 0x0000 0xFFFF Bit 0 chan...

Страница 19: ...d DO7 to turn ON and others to turn OFF IDENTIFIER BITS RTR Data Length 8 byte Data byte HEX Destination MAC ID 10 9 8 7 6 5 4 3 2 1 0 0 1 2 3 4 5 6 7 1 0 0 0 0 0 0 1 1 0 0 0 7 0A 10 64 01 01 00 F0 Ma...

Страница 20: ...device response the DO data 0x000F at byte 2 and byte 3 The value 0x000F means that the status of DO3 DO2 DO1 and DO0 are turned on and others are turned off Via changing the Attribute ID of the Appli...

Страница 21: ...CAN 2057D User s Manual v1 10 April 2015 21 Appendix A Dimension...

Отзывы: