ALM-Horn Series User’s Manual

 

 

ALM-Horn Series 

User’s Manual (Rev1.0, NOV/2020) ------------- 23

 

4.3

 

  Modbus TCP Protocol Description 

 

The  Modbus  protocol  defines  a  simple  protocol  data  unit  independent  of  the 

underlying  communication  layers.  The  mapping  of  Modbus  protocol  on  network  can 
introduce some additional fields on the application data unit.

 

     

Modbus/TCP Application Data Unit 

Transaction ID 

(2 bytes)

 

Protocol

 

ID 

(2 bytes)

 

Length 

(2 bytes)

 

Unit ID

(1 bytes)

FCode

(1 bytes)

Data

 

(0 to 252 bytes)

 

MBAP Header 

Protocol Data Unit 

Figure 5-1

:

 Modbus/TCP Application Data Unit 

 

4.3.1 

MBAP 

 

The  Modbus/TCP  extension  includes  7  additional  bytes  to  the  original  Modbus 

protocol, which allows for transport over the TCP/IP layers. 

A  dedicated  header  is  used  on  TCP/IP  to  identify  the  Modbus  Application  Data 

Unit.  It  is  called  the  MBAP  Header  (MODBUS  Application  Protocol  Header).  The 
MBAP Header consists of 7 bytes of information: 

 

Fields 

Length 

Description 

Transaction Identifier 

2 bytes 

Identification of Request/Response transaction – Copied 
from request to response 

Protocol Identifier 

2 bytes 

0 = Modbus protocol 

Length 

2 bytes 

Number of following bytes - Includes the Unit Identifier 

Unit Identifier 

1 byte 

Identification of remote slave 

Table 5-1: MODBUS/TCP Application Protocol Header

 

 
 
 

Содержание ALM-Horn Series

Страница 1: ...resulting from the use of this product ICP DAS reserves the right to change this manual at any time without notice The information furnished by ICP DAS is believed to be accurate and reliable However...

Страница 2: ...ALM Horn Series User s Manual ALM Horn Series User s Manual Rev1 0 NOV 2020 2 Document Revision Version Date Description of changes Rev1 0 2020 11 04 First release for ALM Horn Series...

Страница 3: ...es 11 2 3 Dimensions 12 2 4 Wire Connection 13 2 4 1 Wire connection define 13 2 4 2 I O connection 13 3 Software 15 3 1 ALM Utility for ALM Horn WF AP Mode 15 3 1 1 Main Screen 15 3 1 2 Controller St...

Страница 4: ...U protocol ALM Horn series device includes 1 channel digital input for any dry contact output such as SA BA FA etc and 1 channel digital output Each device has 4 kinds of alarm tone NC NO input mode s...

Страница 5: ...ice accepts any dry contact to trigger DI input when the alarm been trigger it output from Piezo Transducer LED s open collector DO ALM Horn series include 4 kinds of alarm tone the DIP switch s selec...

Страница 6: ...Dry Contact Sink Dry Contact Level NO Open NC Close to GND Photo Isolation 3750 VDC Input Condition Pulse Width must 200mSec or more Digital Output Channels 1 Output Type Open Collector Sink Max Load...

Страница 7: ...m status Protection Waterproof IP43 Panel Mount Upright Position ESD IEC 61000 4 2 8 kV Air for Random Point EFT IEC 61000 4 4 2 kV for Power Environment Operating Temperature 20 75 C Mechanism Dimens...

Страница 8: ...Series User s Manual ALM Horn Series User s Manual Rev1 0 NOV 2020 8 2 Hardware 2 1 Outward Appearance Figure 2 1 Front Panel Figure 2 2 Back Panel Connector Piezo Transducer output Waterproof membran...

Страница 9: ...M Horn Series User s Manual ALM Horn Series User s Manual Rev1 0 NOV 2020 9 2 1 2 Connector Pin Define Figure 2 3 I O Connector of ALM Horn MRTU BR Figure 2 4 I O Connector of ALM Horn BR ALM Horn WF...

Страница 10: ...g Figure 2 5 Switches on the PCB 2 2 1 Reset to default for ALM Horn WF BR only Remove the back panel Press hold the Reset button on the bottom side over 6 Sec until the Red LED Status Alarm quick fla...

Страница 11: ...ries Figure 2 6 Alarm Tone select switch for DI trigger alarm Figure 2 7 DI Input Mode NO NC select switch Note Change the Input Mode NC NO must restart the power to take effect Dip Switch Switch Inde...

Страница 12: ...es User s Manual Rev1 0 NOV 2020 12 2 3 Dimensions The diagrams below provide the dimensions of the ALM Horn series to use in defining your enclosure specifications All dimensions are in millimeters F...

Страница 13: ...n Series User s Manual Rev1 0 NOV 2020 13 2 4 Wire Connection 2 4 1 Wire connection define The following describe the wire color Figure 2 9 Wire color 2 4 2 I O connection 2 4 2 1 Digital Input DI wir...

Страница 14: ...ual ALM Horn Series User s Manual Rev1 0 NOV 2020 14 2 4 2 2 Open Collector Digital Output DO wiring Figure 2 11 Open Collector Output wiring 2 4 2 3 RS 485 wiring for ALM Horn MRTU Figure 2 12 RS 485...

Страница 15: ...Horn WF ALM Utility available on both Windows Android application to operating and configure the ALM Horn WF Utility Support Windows 7 or later versions and Android 5 0 or later versions The followin...

Страница 16: ...1 2 Controller Status Show the connected controller information user define Locate string RSSI strength Device IP Static IP button for changing device IP in STA mode 3 1 3 DI DO Status Control Show t...

Страница 17: ...1 4 Icon Button ICON function Setup Open the Setup Screen Android versions Setup function under the icon Find Controller Red Led blinking use to find the connected Controller Refresh Refresh status M...

Страница 18: ...e take effect on new setting AP SSID Name 1 Default Controller s SSID in Wi Fi AP mode will be ALM 06 xxxxxx Note xxxxxx is the last 6 characters MAC address of your device Key Type AP mode SSID Key t...

Страница 19: ...7 1 AP mode support only one connection If Multiple devices connect at a same time only first connected devices can access STA Station ALM Controller will auto connect to specific Wi Fi AP PC or Andro...

Страница 20: ...P Scanner for Windows Network Analyzer for Android those are high performance scanner tools on each OS 3 2 USB Utility for ALM Horn MRTU The Utility provides the simple way to configuration ALM Horn M...

Страница 21: ...ata contents of registers Function Code Descriptions 01 0x01 Read Coil Status 02 0x02 Read Input Status 03 0x03 Read multiple Analog Output registers 05 0x05 Force Single Coil 06 0x06 Write single Ana...

Страница 22: ...nary A binary item is represented as a single bit within a data word All binary is packed into 16 bits data words which are accessed using function code 01 and 02 Therefore a single register contains...

Страница 23: ...P Application Data Unit 4 3 1 MBAP The Modbus TCP extension includes 7 additional bytes to the original Modbus protocol which allows for transport over the TCP IP layers A dedicated header is used on...

Страница 24: ...F 1 ON R Table 5 7 FC02 Read DI address 1xxxx Address CH Length Descriptions Range Value Access Type 40011 Always 1 Read Idle Timeout value 16bit Word R Table 5 8 FC03 Read multiple AO address 4xxxx A...

Страница 25: ...eries User s Manual ALM Horn Series User s Manual Rev1 0 NOV 2020 25 Technical Support If you have problems about using the ALM Horn Series device please contact ICP DAS Product Support Email service...

Отзывы: