background image

ELECTRONIC CIRCULATOR FOR HEATING SYSTEMS - Art. P329

ICMA S.p.a. - Heating Technologies - www.icmaspa.it

FI.P329.EN.C  -  1 /2022

Icma SpA - Via Garavaglia, 4 - 20012 Cuggiono (MI) ITALY Tel: +39 02 97249134 - +39 02 97249135 - www.icmaspa.it - [email protected]

Icma SpA - Via Garavaglia, 4 - 20012 Cuggiono (MI) ITALY Tel: +39 02 97249134 - +39 02 97249135 - www.icmaspa.it - [email protected]

2

3

1. INDICATION OF INSTRUCTIONS

This manual contains information and prescriptions marked by the following symbols.

This instruction sheet contains following warning symbols.

The inobservance of the safety provisions marked by the symbol “CAUTION”:
hazard” may endanger the safety of people.

The inobservance of the safety provisions marked by the symbol “CAUTION”:
electricity” may endanger the safety of people, as well as the integrity of

things.

The inobservance of the safety provisions marked by the word “CAUTION”

may endanger the integrity and functionality of the equipment and of the
machines.

The circulators are not to be used to transfer flammable liquids such as

gasoline, oils, gas oil or similar liquids.

The circulators are not to be used to transfer aggressive liquids, such as acids

and sea water.

CAUTION
The removal of the screws can cause the output of hot fluids under high pressure

from heating system. Drain the system or close the isolating valves.

CAUTION

High temperature surface. Pay utmost care to prevent people from getting in

contact with the hot surfaces of the circulator.

CAUTION

Содержание P329

Страница 1: ...20012 Cuggiono MI ITALY Tel 39 02 97249134 39 02 97249135 www icmaspa it sales icmaspa it 1 INSTALLATION AND OPERATION INSTRUCTIONS These instructions include information necessary to assemble and use...

Страница 2: ...FIELD OF APPLICATION 6 3 1 Types of system 6 3 2 Pumped liquids 6 4 INSTALLATION AT SITE 8 4 1 Installation 8 4 2 Permissible installation positions 9 4 3 Motor housing positions 9 5 ELECTRIC CONNECT...

Страница 3: ...rked by the symbol CAUTION electricity may endanger the safety of people as well as the integrity of things The inobservance of the safety provisions marked by the word CAUTION may endanger the integr...

Страница 4: ...c safety precautions should be observed including the following 1 Read and follow all safety instructions and all the important notices on the appliance before installing using and maintaining the cir...

Страница 5: ...all the circulator in an accessible place for future checks and disassembly procedures Foresee enough space for inspections and disassembling To avoid circulator overheating do not place any object on...

Страница 6: ...damages The indicated limit values are binding and cannot be exceeded for any reason whatsoever 3 FIELD OF APPLICATION 3 2 Pumped liquids 3 1 Types of system Circulation of water liquids in hot water...

Страница 7: ...4 20012 Cuggiono MI ITALY Tel 39 02 97249134 39 02 97249135 www icmaspa it sales icmaspa it 7 Ambient temperature Liquid temperature C Min C Max C 0 2 95 10 10 95 20 20 95 30 30 95 35 35 90 40 40 70 T...

Страница 8: ...rocedures Foresee enough space for inspections and disassembling Foresee isolating valves at intake and output before and after the circulator to allow the disassembly without emptying the plant The a...

Страница 9: ...4 3 Pay utmost care to prevent people from getting in contact with the hot surfaces of the circulator Drain the system or close the isolating valves on either side of the pump before the screws are re...

Страница 10: ...voltage of the mains with the rating data All electric information concerning the A1 G413 is on the signaling plate The connection cord must be laid in such a way as it cannot come in contact with the...

Страница 11: ...ivations deactivations through the mains voltage 20 24 h min 7 0 mm max 8 5 mm 6 COMMISSIONING 6 1 Start up of the circulator Absolutely avoid dry operation Start the circulator only after having comp...

Страница 12: ...Operating elements 6 3 Mode of operation Fig 6 1 Selector and LED light LED COLOR DESCRIPTION Green P mode p v Proportional differential pressure The circulator head is proportionally reduced with dec...

Страница 13: ...rapid succession of WHITE colour Following the light signal it s possible to easily vent the heating system as follows 1 Open the air vent valve in the hydraulic circuit above the circulator or open t...

Страница 14: ...ing a flat screwdriver as given in the following table The selection of the right functioning curve depends on the characteristics of the heating system in question and the actual heat demand Factory...

Страница 15: ...clean the impeller Loud noises of water circulation Flashing white LED Air in the system Vent the system 6 4 Automatic detection of the presence of air Vent system LED on The flow is too high Reduce t...

Страница 16: ...t removed through the automatic release process after 100 attempts to restart the circulator it goes into standby and the LED remains red In this case follow the manual procedure described in the next...

Отзывы: