Symptom
Remedy
No display
Check for 24 VAC at thermostat; display is blank when 24 VAC is not present
System fan does not come on
properly
Verify wiring is correct
Check configuration (see “Configuration Mode,” Setting 2, Page 22)
See “Fan Test” (Page 26)
Thermostat turns on and off too
frequently
Adjust temperature differential (see “Temperature Differential,” “Configuration
Mode,” Settings 6, 7 and 8, Pages 23 and 24)
Fan runs continuously
Check fan On/Auto switch, ON position runs indoor fan continuously
Room temperature is not correct
Verify wall hole is plugged with putty or insulation; calibrate thermostat (see
“Configuration Mode,” Setting 13, Page 25)
ROOM displays
Room temperature offset is not zero (see “Configuration Mode,” Setting 13,
Page 25)
Status indicator
Green light – Cooling operation
Red light – Heating operating
Status indicator option ON (see “Configuration Mode,” Setting 16, Page 25)
filter displays
Fan run time has exceeded filter check time set in configuration (see
“Configuration Mode,” Setting 15, Page 25)
To reset counter to zero and clear filter warning, press the and buttons
simultaneously for 5 seconds
EH displays when button is pressed
Thermostat is in
Emergency Heat
mode (see “Operating Modes,” Page 28)
Er displays
Sensor error – check S1 & S2 connections, check remote sensor wire and
connections, use grounded shielded wire for remote sensor
Problem not listed above
Press the Reset button once; display will be refreshed and anti-short cycle
timing will be reset to zero
Troubleshooting