16

11.

   Auxiliary Delay ON

 (0-60 minutes)

Set the delay time in minutes for auxiliary heat to be locked out after a call for second stage. This 
extra savings feature is used to temporarily lock out auxiliary heat devices, allowing just heat pump to 
try to satisfy heat call.
Press the 

 or 

 to select.

Press 

 to advance to the next screen.

CONFIG

HEAT

12.

   Lockout

 (0-8°, SLEEP, COOL-HEAT)

Select the number of degrees set temperature can be changed during keypad lockout. 

SLEEP

 

setting locks thermostat only during the sleep period to prevent after hours tampering. 

COOL-HEAT

 

lockout allows adjustment of the set temperatures to the maximum heat set temperature selected and 
minimum cool set temperature selected.

 

Note:

 

The mode cannot be changed while the thermostat is locked.

Press the 

 or 

 to select.

Press 

 to advance to the next screen.

CONFIG

10.

   Outdoor Lower Setpoint 

(select – – to disable)

Appears only for heat pump with electric backup with outdoor upper setpoint enabled.

 

Note:

 

Select lower setpoint for chart on previous page.

Press the 

 or 

 to select temperature.

Press 

 to advance to the next screen.

CONFIG

Low

WARNING!

Incorrect settings can damage system and/or cause potentially dangerous 

conditions. Use the code described in Configuration Safety Lock.

 

Note:

 

Select upper setpoint for chart on previous page. Select 

 to disable.

Press the 

 or 

 to select.

Press 

 to advance to the next screen.

9.

   Outdoor Upper Setpoint

 (50°F to 25°F, – –) (10°C to -4.0°C, – –)

CONFIG

Hi

13.

   Maximum Heat Setpoint

 (45°F to 90°F) (7°C to 32°C) 

Adjust to control the maximum heat set temperature allowed.
Press the 

 or 

 to select.

Press 

 to advance to the next screen.

CONFIG

HEAT

Содержание i3 2010WR

Страница 1: ...Programmable Thermostat 7 Day 5 2 Day or 5 1 1 Day Programmable Configurable for Multiple Systems Large Display with Backlight Selectable Fahrenheit or Celsius Icon Indicator Lights Relay Outputs Min...

Страница 2: ...on Drill with 3 16 bit hammer screwdriver Specifications Electrical Rating 24 VAC 18 30 VAC 1 amp maximum per output terminal 5 amp maximum total load Temperature Control Range 45 F to 90 F 7 C to 32...

Страница 3: ...ressor come on for 4 minutes after it turns off to protect your compressor When the room temperature is greater than the set cool temperature by the differential temperature the cooling device is acti...

Страница 4: ...and set vacation return dates Flashing The thermostat is in Setup Mode and is searching for a wireless network Flashing Wi Fi is busy Solid The thermostat is not connected to Wi Fi If the thermostat...

Страница 5: ...screws to secure wires CAUTION Be sure exposed portion of wires do not touch other wires 9 Gently tug wire to be sure of proper connection Double check that each wire is connected to the proper termin...

Страница 6: ...ps Y2 2nd stage cool for 2 compressor systems 2nd stage heat for 2 compressor heat pump systems G Fan W1 O B Configurable W1 1st stage heat for non heat pump systems O Cool active reversing valve B He...

Страница 7: ...VAC Cool Compressor Heat 1 Reversing Valve y 2010WR Heating Cooling T H E R M O S T A T Sensor Common S1 SC S2 RH RC C Y1 W1 O B G W2 Optional Remote or Outdoor Sensors Heating Transformer 120 VAC Co...

Страница 8: ...ressor 1 Cool Compressor 2 Heat 1 Reversing Valve 3020WR Heating Cooling T H E R M O S T A T Sensor Common S1 SC S2 RH RC C Y1 W1 O B G W2 Y2 Optional Remote or Outdoor Sensors Heating Transformer 120...

Страница 9: ...e location for mounting the remote sensors 3 Mount the remote sensors using hardware provided 4 Install two strand shielded wire between the S1 terminal on the remote sensor and the S1 terminal on the...

Страница 10: ...Output Chart 1ST Cool 2ND Cool 1ST Heat 2ND Heat 3RD Heat Heat Cool Y1 G YI Y2 G W1 G W1 W2 G W1 W2 AUX G Heat Pump One Compressor Y1 G O Y1 G O Y1 G B Y1 W2 G B Y1 W2 AUX G B Heat Pump Two Compresso...

Страница 11: ...diagram is the code that will unlock the desired configuration setting The smaller numbers indicated by 93 and 82 in the diagram are codes used to lock and unlock your thermostat to prevent tampering...

Страница 12: ...the previous screen Press the or to change settings within each screen Changes are saved automatically To exit configuration mode press Auto exit occurs after two minutes with no icons touched To chan...

Страница 13: ...he or to set differential value Press to advance to the next screen CONFIG 3 2nd Stage Temperature Differential 1 F to 5 F 0 5 C to 2 5 C Note Not for 1010W Set the number of degrees between when stag...

Страница 14: ...Heat Pump with 1 compressor and Cool Active Reversing Valve 6 Minimum Deadband 1 F to 9 F 1 C to 5 C Set the minimum separation between heat setpoint and cool setpoint in Auto Changeover Mode Press th...

Страница 15: ...utdoor Temperature Setpoint Heat pump operation only Gas oil operation only F C Heat Pump with Gas Oil Back Up DF Heat Pump with Gas Oil Back Up DF Outdoor Temperature Setpoint Gas oil operation only...

Страница 16: ...mode cannot be changed while the thermostat is locked Press the or to select Press to advance to the next screen CONFIG 10 Outdoor Lower Setpoint select to disable Appears only for heat pump with ele...

Страница 17: ...CONFIG HEAT VACATION 15 Vacation Cooling Setpoint These work in conjunction with the Schedule mode where you set the date and time of your RETURN from vacation Page 28 Until that date time system will...

Страница 18: ...ss to advance to the next screen 20 Fan Delay Off Time 0 30 60 90 seconds Select the amount of time the fan continues to operate after the cool heat demand has been satisfied Functions for cooling hea...

Страница 19: ...e wireless network as if for the first time Note If the thermostat has been connected to a wireless network before the reset Wi Fi configuration will be the last screen in the Configuration Menu To ea...

Страница 20: ...ack of the thermostat above the terminals and on the front of this book d Reset Wi Fi on thermostat To reset Wi Fi please follow the steps under Wi Fi Reset on Page 19 e Follow the prompts to connect...

Страница 21: ...our Wireless Network a In the list of available networks select the correct network and enter password if password protected b will stop flashing and will display indicating the thermostat is successf...

Страница 22: ...stration Press then press until displays Press to advance from one screen to the next Note Pressing will return you to the previous screen To exit weather press Setting the Time and Date 1 Press then...

Страница 23: ...mode and press HEAT HEAT MODE The possible operating modes for the thermostat are OFF HEAT EM HEAT COOL and AUTO Use to select Auto Mode In this mode the thermostat controls either heating or cooling...

Страница 24: ...s displayed 2 Adjust set temperature so it is 5 degrees below room temperature 3 Cooling should come on within a few seconds 4 Adjust the set temperature 2 degrees above the room temperature and the c...

Страница 25: ...lect the minutes when you want the current period to begin 10 Press to continue 11 The HEAT temperature flashes Use the or to set the desired heat temperature 12 Press to continue 13 The COOL temperat...

Страница 26: ...ed or unlocked View program schedule settings OFF shows when schedule is off SETTINGS show when schedule is on VIEW SCHEDULE SLEEP Mon View REMOTE SENSOR 1 temperature if not used VIEW Remote Sensor V...

Страница 27: ...onth later To set the vacation timer and begin vacation setpoint mode 1 Press to select operating mode 2 Press then press until VACATION appears 3 Press to enter the date and time you plan to RETURN f...

Страница 28: ...L COOL COOL WEDNESDAY 3 WAKE LEAVE RETURN SLEEP HEAT HEAT HEAT HEAT COOL COOL COOL COOL THURSDAY 4 WAKE LEAVE RETURN SLEEP HEAT HEAT HEAT HEAT COOL COOL COOL COOL MONDAY thru SUNDAY Factory Preprogram...

Страница 29: ...ontinued FRIDAY 5 WAKE LEAVE RETURN SLEEP HEAT HEAT HEAT HEAT COOL COOL COOL COOL SATURDAY 6 WAKE LEAVE RETURN SLEEP HEAT HEAT HEAT HEAT COOL COOL COOL COOL SUNDAY 7 WAKE LEAVE RETURN SLEEP HEAT HEAT...

Страница 30: ...minal connections LOCK displays when any button is pressed Thermostat has the button lockout function activated see Lockout Unlock Feature Page 11 on display instead of room temperature Check for a ba...

Страница 31: ...may only operate using an antenna of a type and maximum or lesser gain approved for the transmitter by Industry Canada To reduce potential radio interference to other users the antenna type and its ga...

Страница 32: ...ect tampering improper storage incorrect installation or servicing not performed by the Seller In order to permit the Seller to properly administer the warranty the Buyer shall 1 Notify the Seller pro...

Отзывы: