MONOLITE
4
3 TECHNICAL
SPECIFICATIONS
3.1
MONOLITE 45 GT – 350 GT
Characteristics
Effic. 100%
(stars)
NG max flow
rate G20
NG max flow
rate G30
NG max flow
rate G31
Max flow rate
of flues
kW
kcal/h
kW
kcal/h
kW
kcal/h
%
%
%
m³/h
kg/h
kg/h
kg/h
Medium
Temp.
70°C
Temp.
flow/return
50/30°C
(Efficienty Dir.
92/42/CEE)
MONOLITE 45 GT
52,0
45.000
57,0
49.200
53,0
45.800
98,3
107,5
****
5,64
4,18
4,14
84,04
MONOLITE 70 GT
81,0
70.000
88
76.500
82,0
71.200
98,3
107,5
****
8,76
6,50
6,43
130,52
MONOLITE 95 GT
110,0
95.000
120
103.800 112,0
96.600
98,3
107,5
****
11,89
8,82
8,73
177,16
MONOLITE 125 GT
145,0 125.000
158
136.700 147,0 127.200
98,3
107,5
****
15,65
11,62
11,49
233,19
MONOLITE 160 GT
186,0 160.000
203
175.000 189,0 162.800
98,3
107,5
****
20,03
14,87
14,71
298,45
MONOLITE 210 GT
244,0 210.000
266
229.600 248,0 213.600
98,3
107,5
****
26,28
19,51
19,30
391,57
MONOLITE 270 GT
313,0 270.000
343
295.300 319,0 274.700
98,3
107,5
****
33,80
25,09
24,81
503,62
MONOLITE 350 GT
406,0 350.000
445
382.800 414,0 356.100
98,3
107,5
-
43,82
32,52
32,17
652,92
Efficiency 100%
(N.C.V.)
Temp. flow/return
50/30°C
Medium Temp.
70°C
Heat output
Heat input
Characteristics
Effic. 30%
(stars)
NG min flow
rate G20
NG min flow
rate G30
NG min flow
rate G31
Min flow rate
of flues
kW
kcal/h
kW
kcal/h
kW
kcal/h
%
%
%
m³/h
kg/h
kg/h
kg/h
Medium
Temp.
70°C
Temp.
flow/return
50/30°C
(Efficienty
Dir.
92/42/CEE)
MONOLITE 45 GT
17
15.000
19
16.599
17
15.228
98,5
109
****
1,87
1,39
1,38
27,92
MONOLITE 70 GT
26
23.000
30
25.452
27
23.350
98,5
109
****
2,87
2,13
2,11
42,81
MONOLITE 95 GT
37
32.000
41
35.411
37
32.487
98,5
109
****
4,00
2,97
2,93
59,56
MONOLITE 125 GT
48
42.000
54
46.477
49
42.640
98,5
109
****
5,25
3,89
3,85
78,18
MONOLITE 160 GT
61
53.000
68
58.650
62
53.807
98,5
109
****
6,62
4,91
4,86
98,65
MONOLITE 210 GT
81
70.000
90
77.462
82
71.066
98,5
109
****
8,74
6,49
6,42
130,29
MONOLITE 270 GT
104
90.000
116
99.594
106
91.371
98,5
109
****
11,24
8,34
8,25
167,52
MONOLITE 350 GT
136
117.000
151
129.472
138
118.782
98,5
109
-
14,62
10,85
10,73
217,77
Minimum
output
Minimum
input
Efficiency at 30%
(N.C.V.)
Medium Temp.
70°C
Temp. flow/return
50/30°C
Characteristics
Pressure losses
flue gas side
Chimney
available head
Noise
level
CO
emissions
Nox
emissions
Heat losses through
the chimney
Heat losses through
the casing
Heat losses with
burner off
Flue gas temp. at boiler
output and air at 20 deg. C
Condense
production
Press. losses
water side
Design
Pressure
Total
capacity
Boiler
weight
Electric
supply
Frequency
Insulation
class
Electric
power
mbar
mbar
dB(A) mg/kWh
mg/kWh
%
%
%
°C
kg/h
mbar
bar
l
kg
Volt ~
Hz
IP
W
For condensing
Temp. flow/return
50/30°C
For condensing
Temp. flow/return
50/30°C
For condensing
Temp. flow/return
50/30°C
GAS
For condensing
Temp. flow/return
50/30°C
Temp.
flow/return
50/30°C
(
Δ
T=12K)
MONOLITE 45 GT
0,6
0,5
62,0
0
45
1,50
0,30
0,10
50
6,68
3,0
5
160
200
230
50
IP X0D
150
MONOLITE 70 GT
0,8
0,2
62,5
0
58
1,50
0,30
0,10
50
10,38
8
5
150
220
230
50
IP X0D
150
MONOLITE 95 GT
1,0
0,5
62,5
0
55
1,50
0,30
0,10
50
14,09
12
5
210
280
230
50
IP X0D
150
MONOLITE 125 GT
1,1
0,5
63,0
0
65
1,50
0,30
0,10
50
18,55
22
5
200
320
230
50
IP X0D
150
MONOLITE 160 GT
1,5
0,5
65,0
0
52
1,50
0,30
0,10
50
23,74
12
5
308
520
230
50
IP X0D
300
MONOLITE 210 GT
2,0
0,5
66,0
0
58
1,50
0,30
0,10
50
31,14
22
5
285
590
230
50
IP X0D
300
MONOLITE 270 GT
2,1
0,5
68,0
0
60
1,50
0,30
0,10
50
40,05
16
5
340
680
230
50
IP X0D
300
MONOLITE 350 GT
2,3
0,5
68,0
0
65
1,50
0,30
0,10
50
51,93
11
5
392
1030
230
50
IP X0D
300
Mod. 45 GT – 125 GT
Содержание MONOLITE GT Series
Страница 2: ......
Страница 12: ...MONOLITE 10 4 3 1 SEALED HOT WATER HEATING SYSTEM WITH EXPANSION VESSEL Mod 45 125 Mod 160 270 ...
Страница 23: ......