INSTRUCTIONS FOR USER, 

INSTALLER AND TECHNICAL SERVICE 

CENTRE 

 
 

NEREIX 

 
 

 

ICI Kronos 

 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

ICI Kronos 

 REV. 6  (FW 0.1)  08/04/2010

 

 

 
 
 
 

Библиотека СОК  

Содержание ICI Kronos

Страница 1: ...INSTRUCTIONS FOR USER INSTALLER AND TECHNICAL SERVICE CENTRE NEREIX ICI Kronos ICI Kronos REV 6 FW 0 1 08 04 2010 Библиотека СОК ...

Страница 2: ...tage limits and Directive 89 336 CEE relating to electromagnetic compatibility We recommend to follow the instructions in this manual with great care ICI Kronos controller allows the control and reading of the NEREIX metering stations INDEX 1 MAIN DISPLAY 3 2 MENU 4 2 1 SEASON AND TEMPERATURES 4 2 2 PROGRAM 5 2 3 VACATION 5 2 4 DISPLAY CONSUMPTION 6 2 5 DISPLAY TEMPERATURES 6 2 6 DATE AND TIME 7 2...

Страница 3: ...ure is kept constantly referring to the one set on the display Temperature can be changed by pushing and keys Off General switch off mode Only anti frost function is active Hold down button to access the current day program to modify it see par 2 2 If Anti frost mode is active in the main screen will appear only Heating icon and not appear or the set temperature or the and MENU 20 0 C 19 1 C Monda...

Страница 4: ...t them by acting on the arrow buttons and push Once selected use the arrows to modify and push Ok to confirm Attention Anti frost temperature can be set to Off In this case the function is not active Flow and DHW temperatures can be modified according to the limits set in the board Ok MENU Season Temperatures Program Vacation Display consumption Display temperatures Go back to menu Menu button ESC...

Страница 5: ...is possible to copy the setting from one day to the other After selecting with the button the day you want to copy push a dot will appear on the left side of the day Select the day you need to program using the key the icon will appear on the bottom left Push the button referring to the icon to overwrite the selected day with the setting highlighted by the dot Repeat the operation selecting other ...

Страница 6: ...COOLING Total energy 000015 1 kWh ESC ESC FLOWS Sanitary 1 flow 12345678 L Sanitary 2 flow 00000012 L Sanitary 3 flow 00000000 L Use the arrow key to scroll through the displays and ESC to exit CURR TEMPERAT Room temperature 19 8 C Outdoor temperature 10 2 C Flow temp 50 2 C DHW temp 30 2 C ESC Available if the Master or the single Slave unit are provided with an outdoor probe ...

Страница 7: ...nd time are set by the central unit 2 7 ALARMS Possible failures are displayed here by pressing simultaneously buttons 3 and 4 for five seconds All alarms must be reported to the technical service centre Press ESC to exit 2 8 CONFIGURATION AND LANGUAGE SETTINGS Bus address Values between 1 and 250 No of meters Values between 1 and 3 Litres Impulse Values of 1 10 100 1000 Litres Impulse ESC DATE AN...

Страница 8: ...ace OFF ICI Kronos turns OFF SMS code space ANTIFZ ICI Kronos goes to anti freeze mode Example If the SMS code was 5555555 this command 5555555 MAN 20 brings operating mode to manual with a temperature set of 20 C 2 10 VISUAL MODE Access to Visual mode is possible from DATE AND TIME menu by pressing simultaneously buttons 3 and 4 With this mode on it is not possible to make any requests or changes...

Страница 9: ...up to 90 meters long Never place in the same corrugated cables for transmitting data and power cables Anyway Master BUS cables and ICI Kronos cables can be placed in the same corrugated Note In case of power polarity inversion the board fuse can eventually burn out Restore the correct polarity and replace the fuse CONNECTING THE BOARDS WITH THE TERMINAL BOX CONNECTING ICI KRONOS TO METERING BOARDS...

Страница 10: ...arked with an S Metering boards are usually preset with a resistance and are fitted in a proper terminal box Fitting of Clima boards must be carried out when wiring the ICI Kronos Unstable communication between board and ICI Kronos can occur if no resistance is installed CONNECTING ICI KRONOS TO NEREIX METERING BOARDS WITHOUT TERMINAL BOX CONNECTING ICI KRONOS TO NEREIX BOARDS WITHOUT TERMINAL BOX...

Страница 11: ...5 mm2 which will exit from the corrugate located in the wall Side venting grates 3 must be fitted to the left Remove the tripolar terminal box from the device and connect the conductors following the diagrams on the previous pages Insert the cabled terminal box and fix the device to its back cover IMPORTANT ICI Kronos is powered directly by the NEREIX multi autonomous station board During maintena...

Страница 12: ...li 38 37059 Zevio fraz Campagnola VERONA ITALIA Tel 045 8738511 Fax 045 8731148 info icicaldaie com www icicaldaie com The data reported are indicative only and are not binding Our company reserves the right to introduce alterations at any time as it deems fit and proper for the development of the product ...