HIGH PRESSURE CUTOUT (HPCO) CONTROL
IC-0170/
I
U
-0170
/IU-0220/
IU-0220
Function
Stops the ice machine if subjected to excessive high-side
pressure.
The HPCO control is normally closed, and opens on a
rise in discharge pressure.
Specifications
Cut-out: 4
26
psig ±10
Cut-in: Automatic reset
(Must be below 3
55
psig to reset)
Check Procedure
1. Set the 'ICE/OFF/WASH' switch to 'OFF'.
2. Connect manifold gauge.
3. Hook voltmeter in parallel across the HPCO, leaving
wires attached.
4. Set the 'ICE/OFF/WASH switch to 'ON' - No air
flowing through the condenser will cause the HPCO
control to open because of excessive pressure.
Watch the pressure gauge and record the cut-out
pressure.
n
Warning
If discharge pressure exceeds 4
26
psig and the
HPCO control does not open, disconnect the power
to stop ice machine operation.
Replace the HPCO control if it:
• Will not reset (below 3
55
psig)
• Does not open at the specified cut-out point
13
2
Содержание WU-0100A
Страница 1: ...Undercounter Ice Machines Technician s Handbook Revision Date 1 24 22...
Страница 2: ......
Страница 14: ...THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 17: ...16 How to Read a Serial Number Full Serial Number...
Страница 154: ...WU 0100 WIRING DIAGRAM Self Contained Air cooled 153...
Страница 155: ...IC 0170 IU 0170 IC 0220 IU 0220 WIRING DIAGRAM Self Contained Air cooled 154...
Страница 156: ...Printed Circuit Bards PCB WU 0100 PCB 155...
Страница 161: ...SPACE FOR TECHNICIAN S NOTES...
Страница 162: ...SPACE FOR TECHNICIAN S NOTES...
Страница 163: ...SPACE FOR TECHNICIAN S NOTES...
Страница 164: ...SPACE FOR TECHNICIAN S NOTES...
Страница 165: ......