6.
Operating
(1)
Safety notices
a.There is a possibility of causing an accident of electric shock
after the measurement of insulation resistance is completed, Be
sure to discharge the high voltage charged in the measuring
object.
b.There is a risk of electric shock during the measurement. Be
careful not to touch the measuring terminal and measuring object
during the measurement.
c.Make measurement within the insulation resistance measuring
range, and never lead voltage from outside, or the tester will be
destroyed.
d.Be sure to confirm the position of rotary switch and the
connection of measuring lead with the tester before starting the
measurement.
e.When start the high voltage button, There is a high voltage
about 15V-2500V between “L ”and “E”, Don’t touch the bare part
of meter and be tested object , cause of the danger.
(2) AC voltage test
a.
Don't test over AC 600V or high voltage. It is Dangerous!
b.Connect the measuring Leads
Insert the plug of lead with probe to measuring terminal ACV, and
the plug of lead with clip to measuring terminal G respectively.
c.Connect to the measuring object
Using the rotary switch select the (600V) position. Connect the
probe of red and black lead to the measuring object.
6