33
FIGURE 32
UPFLOW OPPOSITE SIDE CONDENSATE TRAP CONNECTION
REVERSING THE TRAP
UPFLOW UNITS
The trap may be moved to the right
side for right side drainage. Open the
knockout for the drain on the right
side of the cabinet. Remove the
bracket holding the trap from the left
side. Seal the left side drain hole with
a plug provided in the cloth bag with
the furnace. Position the mounting
bracket and trap so that the drain
elbow is centered in the hole on
the right. See Figure 32.
Drill two holes in the cabinet to mount
the bracket. Mount the trap and
bracket to the right side with the drain
elbow pointing through the knockout.
Connect the
1
/
2
-in. pipe and tee as
noted above. Route the drain hoses
behind the control box, cut to the
appropriate length, and connect to the
trap with hose clamps.
IMPORTANT:
DO NOT ALLOW ANY
SAGS OR KINKS IN THE HOSES.
This prevents proper condensate
flow.
IMPORTANT:
Do not connect into
a common drain line with an air
conditioner evaporator coil drain
located above the furnace. A blocked
or restricted drain line can result in
overflow of the coil pan and negate
the furnace blocked drain shutoff
control.
DOWNFLOW UNITS
To convert to left side drainage, first
remove the drainage hoses from the
trap. Remove the trap from its
mounting bracket, rotate it 180°, and
mount in place with the drainage
elbow pointing to the left. Reattach
the drain hoses. Remove the plastic
drainage knockout from the left side.
See Figure 33.
IMPORTANT:
When changing to the
left side, interchange the rubber
bushing on the right side with the hole
plug on the left side. The hole plug
must be in place to assure that the
control compartment is sealed.
As of September 2, 2006, to convert
downflow models to left-hand drain, a
kit (RXGY-H01) must be ordered from
the distributor. The kit includes a 24”
piece of
1
⁄
2
” black PVC pipe, a 2”
rubber grommet, a 1-5/8” plug and
instructions. Note the location of the
alternate drain hole as shown in
Figure 33.
To convert to left side drainage, first
remove the drainage hoses from the
trap. Remove the trap from its
mounting bracket, rotate it 180
degrees and mount in place with the
drainage elbow pointing to the left.
Reattach the drain hoses.
Remove the plug from the 2” alternate
drain hole (see Figure 33) and
replace it with the 2” rubber grommet
supplied in the RXGY- H01 downflow
alternate drain kit. Also, remove the
1-5/8” grommet supplied in the
primary drain hole and replace it with
the 1-5/8” diameter plug that is also
supplied in the RXGY-H01 downflow
alternate drain kit. Both the hole-plug
and grommet must be in place to
insure a good seal in the burner
compartment.
A length of
1
/
2
” black PVC pipe is also
provided in the RXGY-H01 downflow
alternate drain kit. Glue one end of
the pipe to the elbow in the trap. Cut
the pipe so that it extends through the
alternate drain hole in the left side of
the cabinet one inch (see Figure 33).
Connect the
1
/
2
” PVC tee (supplied
with the furnace) to the pipe with a 1-
3/4” riser. Use the 1-5/8” plug
supplied in the RXGY-H01 downflow
alternate drain kit to seal the right side
drainage hole.
CUT DRAIN HOSES AS
REQUIRED
AND CONNECT TO
INLETS ON TOP
OF CONDENSATE
TRAP
DRAIN
RISER
TEE
DRAIN
EXTENSION
PROPER DRAIN SLOPE REQUIRED
(NO KINKS ALLOWED)
CONDENSATE TRAP
IFC MOUNTING
PLATE
TO FLOOR
DRAIN
IMPORTANT:
Do not connect into a
common drain line with an air
conditioner evaporator coil drain
located above the furnace. A blocked
or restricted drain line can result in
overflow of the coil pan and negate
the furnace blocked-drain shutoff
control.
FILLING THE TRAP
FILL THE TRAP ASSEMBLY WITH
WATER BEFORE OPERATING THE
FURNACE.
Do this by removing the
drain hose from the trap or from the
connection to the secondary coil.
Pour about a cup of water into the
vent trap. Any excess water flows into
the house drain when the trap is full.
I394
FIGURE 33
DOWNFLOW OPPOSITE SIDE CONDENSATE TRAP CONNECTION
TEE
DRAIN
EXTENSION
DRAIN VENT
CONDENSATE TRAP
TO FLOOR
DRAIN OR
CONDENSATE PUMP
ALTERNATE DRAIN HOLE
LOCATED HERE ON JACKET.
(REMOVE PLASTIC PLUG AND
REPLACE WITH GROMMET).
EXISTING DRAIN HOLE. PLUG
WITH 1
5
⁄
8
” PLUG SUPPLIED
IN KIT
ROTATE TRAP 180° AND
INSTALL RIGID PIPE FROM
ELBOW TO OPPSOITE SIDE
OF JACKET AS SHOWN
I394