![Ice Qube 1IQ0000EVZ2 Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/ice-qube/1iq0000evz2/1iq0000evz2_operation-and-installation-manual_610065012.webp)
12
Rev. 2
Press
“3”
to continue. The “Alarm” LED will flash and the display will show “ALL” indicating the “ALL”
alarm on/off status. Press
“3”
and the display will show either “ON” or “OFF”, indicating current alarm
status. Press
“1”
or
“2”
to toggle the mode as desired. If the “OFF” mode is selected, no alarms will
activate and the audible on/off select and POA, Power Off Alarm, functions are skipped.
Press
“3”
to continue. The “Audible” LED will flash and the display will show “AUD”, indicating the
audible alarm on/off status. Press
“3”
and the display shows “ON” or “OFF” indicating the current audible
alarm status. Press
“1”
or
“2”
to toggle the mode desired.
Press
“3”
to continue. The “Alarm” LED will flash and the display will show “POA”, indicating the Power
Off Alarm status. Press
“3”
and the display shows “ON” or “OFF” indicating the current alarm status.
Press
“1”
or
“2”
to toggle the mode desired.
(Version 3.18 and later only)
Press
“3”
to continue. The “C” LED will flash and the display will show either “F” for degrees Fahrenheit
or “C” for degrees Celsius. Press
“1”
or
“2”
to toggle the mode desired.
Press
“3”
to continue. The “Code” LED will flash and the display will show “PIN”. To set a new user PIN
code, press
“1”
. The display will flash “4”, prompting an entry of a four button sequence using the
“1”,
“2”, “3,
and/or
“4”
buttons. Any sequence of the four buttons may be programmed as the code. As the
buttons are pressed, the display will show the number of buttons that were pressed.
Note: After pressing a button, there will only be 5 seconds to press the next button. If the next button is
not pressed within the allotted time, the system will default to no PIN code, indicated by “0” on the
display. Once the sequence is entered the display will no longer flash, and will show “4”.
To program the no PIN code mode, press
“2”
and the display will show “0”, indicating no PIN code. With
no PIN code, pressing any button will permit access to the program.
•••CAUTION•••
ALWAYS RECORD THE SELECTION SEQUENCE (PIN CODE) AND STORE IN A SECURE PLACE
Press
“3”
to continue. The “filter” LED flashes and the display will show “FIL”, indicating the filter alarm
day quantity selection. Press
“3”
and the display will show the number of days that the alarm is set in half
day increments. Note that the alarm is based on compressor run time. (Example: 10.5 indicates that the
alarm will activate every ten and a half days or 252 hours of compressor run time.)
Press
“1”
or
“2”
to vary the desired number of days. Programming “0” days will disable the alarm.
Note: The required number of days to set this alarm will be determined by the ambient air conditions.
Programming of the microprocessor is now complete. Press
“3”
to review all of the settings. Press
“4”
to
enter the selected settings and to return to the normal operating mode.
Note: if “4” is not pressed, any changes to the program settings will not be saved.
Содержание 1IQ0000EVZ2
Страница 7: ...7 Rev 2 Figure 1 Enclosure Installation Figure 2 Push to Connect Fitting Ambient Side Enclosure Side ...
Страница 9: ...9 Rev 2 Figure 4 Terminal Block Figure 5 Power Terminal Block ...
Страница 16: ...16 Rev 2 Schematic Wiring Diagrams 120V 220V 230V Figure 8 IQ351153 Rev A ...
Страница 17: ...17 Rev 2 400V 460V 480V Figure 9 IQ351154 Rev A ...
Страница 18: ...18 Specification Drawing 1000EVZ2 Figure 10 ...
Страница 19: ...19 Rev 2 2000EVZ2 Figure 11 ...
Страница 20: ...20 Rev 2 3000EVZ2 Figure 12 ...
Страница 21: ...21 Rev 2 4000EVZ2 Figure 13 ...
Страница 22: ...22 Rev 2 5000EVZ2 Figure 14 ...
Страница 23: ...23 Rev 2 6000EVZ2 Figure 15 ...
Страница 24: ...24 Rev 2 8000EVZ2 Figure 16 ...
Страница 25: ...25 Rev 2 10000EVZ2 Figure 17 ...
Страница 26: ...26 Rev 2 12000EVZ2 Figure 18 ...
Страница 27: ...27 Rev 2 14000EVZ2 Figure 19 ...
Страница 28: ...28 Rev 2 17000EVZ2 Figure 20 ...
Страница 29: ...29 Rev 2 20000EVZ2 Figure 21 ...
Страница 36: ...36 Rev 2 Notes ...