MFI Series
Control System Diagnostics
Page
23
The Control System consists of:
●
Control Board
●
Water Sensors
●
Ice Sensors
●
High Pressure Cut Out
●
Low Pressure Cut Out
If the unit is
OFF
, check the
control board:
1. Is the Power
OK
light on? If not check power to the unit. If it has power, and the Power
OK
light is
not
on,
check the high pressure and low pressure cut outs. If they are both closed, replace the board. If the
POWER OK
light is
ON,
go to the next step.
2. Is the Water
OK
light on? If it is, go to the next step. If not, check the water level in the reservoir. If there is
water in the reservoir, check that the water sensor is plugged in. To check the water sensor:
a. Unplug the water sensor.
b. Pull the water sensor from the reservoir.
c. Place one ohmmeter lead on the sensor’s plug and the other on the sensor’s tip. The meter should
show nearly zero (0) resistance. If it reads infinite resistance, check the tip for corrosion. If it is clean and
still reads open, replace the sensor.
OR, connect a copper wire to the wire where the water sensor plugs into and place the other end in the
water. The
WATER
OK
should go
ON.
If it does not, replace the board.
3.
Ice sensor Check
. Is the
BIN FULL
light
OFF
? If it is
OFF
and the
SERVICE
light is
OFF
and the unit is not
running, replace the control board.
a. If it is
OFF
and the auger motor is running but the compressor is not, check the compressor contactor coil.
b. If it is
ON
, the ice sensors may be blocked. Remove them and check for mineral scale.
4.
High pressure
cut out check.
a
.
Disconnect electrical power.
b. Pull the wires off the high pressure cut out.
c. Use an ohmmeter to determine if the switch is
OPEN
. If it is, check the discharge pressure. If the
discharge pressure is less than 300 PSIG, replace the high pressure cut out.
d. If the high pressure cut out is open and the system has high discharge pressure, check for the cause.
5.
Low pressure
cut out check.
a.
Disconnect electrical power.
b. Pull the wires off the low pressure cut out.
c. Use an ohmmeter to determine if the switch is
OPEN
. If it is, check the suction pressure. If the suction
pressure is greater than 20 PSIG, replace the low pressure cut out.
d. If the low pressure cut out is open and the system has low suction pressure, check for the cause.
Содержание MFI
Страница 2: ......
Страница 8: ...MFI Series For The Installer Page 2 ...
Страница 38: ...MFI Series MFI0500 Wiring Diagram Page 32 Wiring Diagram MFI0500 Air MFI0500 Water ...
Страница 39: ...MFI Series MFI0800 Wiring Diagram Page 33 Wiring Diagram MFI0800 Air MFI0806 Air MFI0806 Water W BK ...
Страница 40: ...MFI Series MFI0805 1255 Wiring Diagram Page 34 Wiring Diagram MFI0805 MFI1255 Air ...
Страница 41: ...MFI Series MFI1256 Wiring Diagram Page 35 Wiring Diagram MFI1256 Air ...