OPERATING & MAINTENANCE MANUAL

 – 

CONSOLE HYBRID WATER-COOLED AIR CONDITIONER (CHW)

6

Daily Programming

Press [On/Off] to select Schedule  
(Schedule is flashing)
1.  Press [Mode] key to select Edit “Set Schedule.”
2.  Use [Up] and [Down] to select Day.
3.  Press [Mode] to edit time.
4.  Use [Up] and [Down] to select Time. 
 

(Adjustable in 10 minute increments)

5.  Press [Mode] to edit heat setting.
6.  Use [Up] and [Down] to select temperature.
7.  Press [Mode] to edit cool setting.
8.  Use [Up] and [Down] to select temperature.
9.  Press [Mode] to set next time frame.
10.  Follow the screen, and repeat steps 2 through 9 to 
 

adjust 7 day schedule programming.

11.  Press [Fan] when complete.

 
Below is the default program: 
The default selection is 5-2 day program. 

Changing Program Schedule and Temperature Limits 

Press [On/Off] twice to select Settings  
(Settings is flashing)

1.  Press [Mode] key to select Edit “Settings.”
2.  Use [Up] and [Down] to select 7 Day or 5-2 Day.
3.  Press [Mode] to edit Heat Temperature Limit.
4.  Use [Up] and [Down] to set temperature. 

Default internal setting: Heat limit 90°F

5.  Press [Mode] to edit Cool Temperature Limit.
6.  Use [Up] and [Down] to set temperature. 

Default internal setting: Cool limit 60°F

7.  Press [Fan] when complete. The cool limit setting 

should be at least 4°F higher than the heat limit 

 setting.

• 

The cool limit setting is 55°F to 95°F

• 

The heat limit setting is 51°F to 91°F

 

Exit Internal Setting and Return to Normal Mode

1.  Press [Fan] to confirm and return to normal mode.
2.  If no key is pressed for 15 seconds, it will return to 

normal mode automatically.

Auto Mode

• 

To activate auto mode, press the mode  

 

button until AUTO displays. 

• 

Press up/down arrow keys to set  

 

desired heat temperature.

• 

Wait 5 seconds for cool to appear.

• 

Press up/down arrow keys to set desired cool 

 temperature.

• 

The unit will automatically cycle between heat and    

 

cool modes if unit exceeds desired set points. The    

 

temperature reading that is on constant display is the  

 

ambient room temperature. 

Internal Setting

Enter internal setting mode by pressing and holding [Mode] 
key for 5 seconds

Time Setting

Set Clock/Day is flashing
1.  Press [Mode] key to select Edit “Clock/Day.”
2.  Use [Up] and [Down] keys to adjust hours (12 hr).
3.  Press [Mode] to select minutes.
4.  Use [Up] and [Down] keys to adjust minutes.
5.  Press [Mode] to select days.
6.  Use [Up] and [Down] keys to adjust days 
 

Press [Fan] when complete.

EVENT

TIME

HEAT

COOL

MON-
FRI

WAKE
LEAVE
RETURN
SLEEP

6:00 AM
8:00 AM 
6:00 PM 
10:00 PM

70º F (21º C) 
62º F (17º C) 
70º F (21º C) 
62º F (17º C)

78º F (26º C)
85º F (29.5º C) 
78º F (26º C) 
82º F (28º C)  

SAT-
SUN

WAKE
LEAVE
RETURN
SLEEP

6:00 AM
10:00 AM 
6:00 PM 
11:00 PM

70º F (21º C) 
62º F (17º C) 
70º F (21º C) 
62º F (17º C)

78º F (28º C)
85º F (29.5º C) 
78º F (26º C) 
82º F (28º C)  

6:08

AM

MON
WAKE

Содержание CHW

Страница 1: ...Console Hybrid Water Cooled Air Conditioner CHW OPERATING MAINTENANCE MANUAL World Class Comfort ...

Страница 2: ...BS FINISH N A DRAWING BY DATE TITLE SIZE DWG NO REV SCALE NONE UNLESS OTHERWISE SPECIFIED SHEET 1 OF 1 DO NOT SCALE DRAWING HYBRID C WSHP WITH SLIDING CHASSIS CABINET GENERAL ASS Y DIMENSIONS ARE IN INCHES TOLERANCES FRACTIONAL 1 32 ANGULAR MACH BEND 1 TWO PLACE DECIMAL 03 THREE PLACE DECIMAL 015 This drawing is the intellectual property of Ice Air LLC and consists of confidential data belonging s...

Страница 3: ...y will be explained in a separate instruction sheet specific to that option On behalf of ICE AIR and our network of distributors and dealers we are happy to welcome you to our base of satisfied customers CONSUMER SAFETY AND OPERATING NOTES FOR SAFE AND OPTIMAL ENJOYMENT OF YOUR ICE AIR CHW UNIT PLEASE READ THE FOLLOWING CONSUMER SAFETY AND OPERATING NOTES CAREFULLY BEFORE OPERATING YOUR EQUIPMENT ...

Страница 4: ...tions must be maintained for proper unit operation Unobstructed air flow into and out of the unit room enclosure cabinet Therefore Do not place furniture rugs or objects directly in front of underneath or against the unit cabinet front Do not place plants fabrics or objects on top of or blocking the enclosure discharge grille at the cabinet top Do not block the top of the cabinet with drapes or cu...

Страница 5: ...own Permanent over ride mode ON OFF ON OFF MODE Set operation mode Internal Setting FAN Set fan speed Confirm USER INTERFACE PUSH BUTTONS Operation Normal Mode 1 Press ON OFF to turn on thermostat 2 Press Mode to change the system mode 3 There are three operation modes Cool Mode Heat Mode Auto Mode Cool Mode To activate cooling mode press the mode button until COOL displays Press up down arrow key...

Страница 6: ...t limit setting The cool limit setting is 55 F to 95 F The heat limit setting is 51 F to 91 F Exit Internal Setting and Return to Normal Mode 1 Press Fan to confirm and return to normal mode 2 If no key is pressed for 15 seconds it will return to normal mode automatically Auto Mode To activate auto mode press the mode button until AUTO displays Press up down arrow keys to set desired heat temperat...

Страница 7: ... 95 F Resolution 0 5 C 1 F Operating temperature 0 50 C 32 122 F Storage temperature 5 50 C 23 122 F MAINTENANCE SERVICE CAUTION to prevent injury or death due to electrical shock or contact with moving part turn off the disconnect switch before servicing this unit IMPORTANT NOTE It is not the intent of this maintenance manual to correct any installation deficiencies If you have any doubt about th...

Страница 8: ...ollowing cleaning To access the components within the roomside section of the unit disconnect the power to the unit and then remove the unit chassis front cover by unscrewing the 8 hex head retaining screws that hold the front cover in place use a hex head driver You will then have access to the following components EVAPORATOR COIL Check the coil for cleanliness and uniformity of fins If the coil ...

Страница 9: ...tem with water problem history it is best to establish a periodic maintenance program It is the building s responsibility to maintain a water system that should provide your unit with treated and filtered water to keep water flowing freely through your equipment Generally if the water flow exceeds 3 gpm per tonthe water elocities should keep your coil free of scaling and debris that could lead to ...

Страница 10: ...te Look for wiring errors Check for loose screw connections in both line and low voltage terminals Check the water supply piping for proper water connection Check for dirty filters Check indoor fan for proper operation Check that unit did not cycle off on thermostat Check for fault codes on the control board consult the trouble shooting guide 2 If checks above fail to reveal operating problem and ...

Страница 11: ... ICE AIR INSTALLATION MANUAL AND PROCEDURES MUST BE SERVICED BY QUALIFIED TRAINED PERSONNEL ELECTRIC SHOCK HAZARD DISCONNECT FROM LIVE ELECTRIC CIRCUIT BEFORE SERVICING MOVING PARTS HAZARD DISCONNECT FROM LIVE ELECTRIC CIRCUIT BEFORE SERVICING UNIT MUST BE OPERATED WITH ALL CHASSIS SHEET METAL PARTS PROPERLY IN PLACE UNIT MUST BE OPERATED WITH ALL ENCLOSURE CABINET PARTS IN PLACE READ THIS ENTIRE ...

Отзывы: