background image

Due to ICE AIR’s ongoing product development programs, the information in this document is subject to change without notice.

9

Troubleshooting

IMPORTANT: It is not the intent of this maintenance manual to 
resolve any problems with the operation of your ICE AIR unit. 
Please contact a trained servicer or building maintenance 
staff immediately if your unit fails to perform properly.

1.  Contact a trained service technician to conduct full unit 

diagnostics and repair to equipment. 

2.  Record any unit that does not operate noting the unit serial 

number on your report.

If unit is not operating, conduct the following checks:

1.  Check the electrical connections.
2.  Check the voltage and current against the electrical 

specifications on the unit nameplate.

3.  Look for wiring errors. Check for loose screw connections in both 

line and low voltage terminals.

4.  Check the water supply piping for proper water connection.
5.  Check for dirty filters.
6.  Check indoor fan for proper operation.
7.  Check that unit did not cycle off due to improper thermostat 

settings.

8.  Check for fault codes on the control board – consult the Board 

Troubleshooting Table.

 RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.

 

WARNING: 

ICE AIR will not be responsible for any injury 

or property damage arising from improper service or service 
procedures. If you install or perform service on this unit, you 
assume responsibility for any personal injury or property 
damage which may result. Many jurisdictions require a license 
to install or service heating and air conditioning equipment.

 

WARNING HIGH VOLTAGE:

 

Disconnect all power before 

servicing or installing unit. Multiple power sources may be 
present. Failure to do so may cause property damage,  
personal injury or death.

Board Troubleshooting Table

Display (Fault Code)

LED

Troubleshoot Guide

Yellow

Green

Red

Normal Mode

OFF

ON

OFF

Normal Operation

High Pressure

OFF

OFF

FLASH

Low/no water flow, dirty coax coil, cap tube blockage, entering water temp is too high

Low Pressure

FLASH

OFF

OFF

Low charge, dirty filter, dirty evap coil

Evaporator too cold

FLASH

ON

FLASH

Dirty filter, dirty evap coil, fan motor failure, low gas

Coaxial winter protection

FLASH

ON

OFF

Water too cold during off mode

Temperature probe failure

OFF

FLASH

OFF

Loose/disconnected probe wire, bad probe

High/low voltage

OFF

OFF

ON

Site voltage unstable, bad transformer

Condensate over flow

OFF

ON

ON

Clogged condensate drainage

Coaxial water too cold

ON

OFF

OFF

Water too cold during on mode, low gas

Содержание 5CHPW09

Страница 1: ...CHPW Slope or Flat Top Console Unit Water Source Heat Pump WSHP Unit ELA 8842 Installation Manual ...

Страница 2: ...se to install or service heating and air conditioning equipment WARNING HIGH VOLTAGE Disconnect all power before servicing or installing unit Multiple power sources may be present Failure to do so may cause property damage personal injury or death To ensure that the unit operates safely and efficiently it must be installed according to these installation instructions and all local codes and ordina...

Страница 3: ...against the Bill of Lading Ensure all components are intact upon delivery and free from damage Note any damage on the delivering carrier s Bill of Lading 2 The ICE AIR unit s arrive prefabricated with an enclosure Ensure both the unit and the enclosure are properly attached 3 Make sure the floor is level in both directions so the unit s airflow will be aligned Confirm adequate drainage is availabl...

Страница 4: ... amperage of the dedicated electrical service to the unit is correct and the unit can reach the power supply 6 Position the unit so the air filter can be removed easily and required maintenance can be performed without interference 7 A minimum obstructed distance of 36 should be kept around the unit IMPORTANT To avoid permanent damage to the unit DO NOT operate during construction in an open space...

Страница 5: ...s and field installer removes the plugs on the field piping side Water piping terminates in the same location regardless of the connection and valve options Filter Installation Each unit is delivered with a filter for the filter rack which can be found at the bottom of the unit as shown below In order to install the filter slide the piece horizontally into the slot Ensure the filter is effectively...

Страница 6: ...ction is made by connecting the incoming line voltage wires to the terminal block Volt Operation All commercial units are factory wired for specific voltages These include 115 VAC 208 230 VAC 265 277 VAC For 230 volt single phase operation the primary voltage to the transformer must be changed NOTE Failure to change the primary voltage lead when using 230 VAC line voltage may result in electrical ...

Страница 7: ...ween 60 90 F The use of a closed circuit evaporative cooling tower with a secondary heat exchanger between the tower and the water loop is recommended If an open type cooling tower is used continuously chemical treatment and filtering will be necessary System Start System Cleaning and Flushing Cleaning and flushing the unit is the most important step to ensure proper start up and continued efficie...

Страница 8: ... Pan and Drain Hoses Check the unit condensate drain pan and drain hoses annually to ensure proper condensate drainage If any foreign matter build up in the drain pan is found clean the drain pan and drain hoses frequency of cleaning depends on the level of dirt and pollutants that may be present in the indoor environment Evaporator Coil Check and clean if necessary the unit evaporator coil annual...

Страница 9: ...OGNIZE THIS SYMBOL AS A SAFETY PRECAUTION WARNING ICE AIR will not be responsible for any injury or property damage arising from improper service or service procedures If you install or perform service on this unit you assume responsibility for any personal injury or property damage which may result Many jurisdictions require a license to install or service heating and air conditioning equipment W...

Страница 10: ...e Heat limit setting is 51 F to 91 F Operation Normal Mode 1 Press ON OFF to turn on thermostat 2 Press MODE to change the system mode 3 There are three operation modes Cool mode Heat mode Auto mode Cool Mode 1 To activate Cool mode press the MODE button until COOL displays 2 Press UP DOWN arrow buttons to your desired temperature 3 Compressor will cycle when temperature reaches the set point Afte...

Страница 11: ...usted 4 In Auto mode Heat set point will be set first and press UP or DOWN to set the Heat set point Press FAN to confirm the Heat set point Cool set point will be set second and press UP or DOWN to set the Cool set point 5 Permanent Override will be canceled if user changes the operation mode or turns off the unit 6 Hold FAN button 5 seconds to cancel the Permanent Override mode Set Day and Time ...

Страница 12: ...n speed is manually selected the fan will continue to blow Heating Cycle Set the thermostat for Heating If applicable the motorized valve opens as long as the thermostat calls for Heating This sends a 24 volt signal to the terminal to the compressor contactor and the compressor starts At the same time a 24 volt signal flows through the fan relay and the blower starts in HIGH speed if the unit is i...

Страница 13: ... system failures complete the following checks and data entries before the system is put into full operation Temperatures Circle F or C Antifreeze __________Type __________ Pressures Circle PSIG or kPa Allow unit to run 15 minutes in each mode before taking data Do not connect service manifold gauges during start up unless instructed by ICE AIR service tech Cooling Mode Heating Mode Return Air Tem...

Страница 14: ...ping Orientation LH Return R Piping Orientation RH Return U Piping Orientation Universal Allows For Field Conn On Either Side X Piping Orientation Not Applicable Item Matrix Name Code String Value Description 12 WIRE WHIPS A Wall mounted with 6 5 foot wire whip B Wall mounted with 10 foot wire whip C Wall mounted with 12 foot wire whip D Wall mounted with 30 foot wire whip E Wall mounted with 50 f...

Страница 15: ...S M Manual Air Vent T Bleed Tee X No Air Vents 21 VALVE PACKAGE ASSEMBLED OR SHIPPED LOOSE A Assembled S Shipped Loose X None 22 SECONDARY DRAIN PANS G Power Coated Galvanized Steel Secondary Drain Pan S Stainless Steel Secondary Drain Pan P Plastic Secondary Drain Pan X No Secondary Drain Pan 23 SECONDARY OVERFLOW SWITCH E Electronic Secondary Overflow Switch X No Secondary Overflow Switch 24 SEC...

Страница 16: ...bligation beyond the terms of these express warranties or to state that the performance of the product is other than that published by Ice Air General Conditions The above warranties are void if Ice Air s equipment has been damaged misused subjected to abnormal use or service or its serial number has been altered defaced or removed or payment for the equipment is in default Ice Air is not responsi...

Отзывы: