1 5
The power factor controller is provided with pass word facility to
prevent alteration of configuration items by unauthorised persons. The
configuration items can be changed by following the sequence given
below.
With power applied to the meter, press & keys together
for three seconds. The display indicates enter pass word as EP- - - -
The valid pass word set in configuration item new pass word has to
be entered by using shift, increment and enter keys (refer changing the
configuration items for using shift, increment and enter keys). After valid
pass word is entered the meter enters into program mode by showing it in
display as P r o g
Note:
If the user enters the enter pass word for the first time, or if the user
fails to remember the pass word set in new pass word, the default pass
word
‘0386’
can be entered.
In program mode, the configuration items can be selected by pressing
the index (#) key. The heading displays are used to differentiate the various
configuration items.
4
4
4
4
4
44444
Run mode display pages
Press # key one by one, run mode display pages as follows:
Page 1 - Ld 0.51
Power factor
Page 2 - q.692.4
Actual total kVAr
Page 3 - r.832.4
Target/required kVAr
Page 5 - Alr 01
Alarm status
Page 4 - CT nil
CT/PT polarity status