52
Modbus / Electric Water Heaters
Central Control Board Major State Definitions
Table 44. ModBus / Electric Water Heaters Central Control Board (CCB) State
Value
State
0
Off (Standby)
6
Heating
8
Fault
Energy Management System (EMS) Control
Commercial Electric water heaters with Xi controls use a single bit setting method. Within the EMS Mode-Status point, one bit
command (bit 15) sets it in EMS mode, and other ends EMS mode. Once in EMS mode, another bit command (bit 0) enables heating;
another disables heating.
Once in EMS mode the EMS Mode Refresh command must be periodically issued which clears a third bit (bit 14) to maintain EMS
mode, otherwise the heater will end EMS mode and resume normal operation.
Table 45. ModBus /Electric Water Heaters Energy Management System (EMS) Control
Decimal
Hex
Value
Response
3840
0x0F00
No EMS control
0 / 0x000
3841
0x0F01
Put into EMS Mode^
49152 / 0xC000
0000
0x0000
EMS Disable heating^
49152 / 0xC000
0001
0x0001
EMS Enable heating^
49153 / 0xC001
3584
0x0E00
EMS Mode Refresh^ (must write within 30 seconds or
EMS mode ends.) 15 seconds or less recommended
49152 / 0xC000 or 49153 / 0xC001 depending
on whether or not heating is enabled.
NOTE:
The start of a heating cycle also depends on other factors, like
Tank Temperature
dropping below Setpoint – Differential and
External
T’stat Call for Heat
if that option is enabled.
^Depending on when you poll the register, you may read bit 14 as 1, which is why a “C” (in hexadecimal form) might briefly reply with
“8”. This is due to the control setting this bit and if it not cleared periodically by the Modbus command, heating is disabled.
After disabling EMS mode with write of 3840, read-back might have bits 14 and 1 possibly still set. To make sure these bits are clear,
write a 0000 to clear bit 1 and 3584 to clear bit 14.
Fault Codes and Warnings
Note:
Any Fault not listed is an internal CCB failure fault.
Table 46. BACnet/Electric Water Heaters Fault Codes and Warnings
Index Range
(Decimal)
Index Range
(Hex Code)
Value
0
0
0x000
0x000
Okay (No Fault)
1
6
0x001
0x006
Memory
24
0x018
Incorrect Model
51
56
0x033
0x038
Power Monitor
69
72
0x045
0x048
Temperature Probe Open or Short
153
154
0x099
0x09A
Communications Fault
165
0x0A5
High temperature ECO (Energy Cut Off)
175
0X0AF
Safety Relay Closed fault
176
188
0x0B0
0x0BC
CCB internal errors
193
194
0x0C1
0x0C2
Processor Clock
198
201
0x0C6
0x0C9
Non-volatile Memory
205
217
0x0CD
0x0D9
Powered Anode
431
0x1AF
Safety Relay Opened fault
1037
1037
0x40D
Element Open Warning
Содержание Mirius
Страница 54: ...54 NOTES...
Страница 55: ...55 NOTES...