Technical specification:
Type:
UWI-IQ
Software:
UWI V40.009 & IQRF V41.002/OS4.00
Purpose:
Transmission of two input signals from one UWI-IQ by wireless to two relay outputs and loop
option of the second UWI-IQ unit, which is configured into the wireless link (peer to peer) or to uCU-IQ system by
compatible communication protocol and messages.
Wireless communication:
868 MHz band, recommended channel in the range from 56 to 60
UWI-IQ wireless loop (PEER to PEER net) or configuration into a system with the wireless control panel
µ
CU-IQ
(STAR net wireless system configuration)
ICAS wireless communication protocol, zone supports, ICAS MASH architecture support,
compatible with
µ
CU-IQ,
certified IQRF radio-module
compatible to RF monitor PC tool for configuration and monitoring
variants with internal or external antennas
Recommended ext. antenna: 868 MHz 5dBi whip
Power:
External power supply voltage in the range from 9V to 24V DC
Current consumption standby:
< 5 mA (Normal - only green Led indication)
Max. current consumption:
< 90mA (Test mode+local alarm +local fault -all leds lighting, both relays on and loop output in fire alarm)
Testing
ByTest/Reset push-button - the short press from Normal will trig a TEST mode - Test Leds is lighting ,test message (T) is
sent by SPI and forwarded by the radio-module. The radio-communication range can be tested this way
By long press of the TEST/RESET push button / till lit of both red and yellow at the same time/ set Diagnostic mode and
Local Alarm/Fault will control in Diagnostic mode also the unit outputs /relays and loop output/. The inputs and outputs
response can be tested without radio-communication or without configuration into a system this way
Delay/input filter:
Adjustable delay - pre-alarm period in steps 4s, default set is 2 samples of pre-alarm.
Output delay
Adjustable delay from alarm/fault message receiving to outputs activation in steps 4s (default set is 0)
Configuration into system :
By the RF monitor V.16 and higher ( PC application) and DS-IQ module
Configurable parameters:
By the RF monitor PC tool (UWI-IQ Setting page)
Input delay
255 steps ( one step is about 4s)
Default 2
Output delay
255 steps ( one step is about 4s)
Default 0
INP 1 (Fire input) level Normal open / Normal closed
Default NO
INP 2 (Fault input) level Normal open / Normal closed
Default NO
Q response
Disabled / Enabled
Default Disabled
Hush response
Disabled / Enabled
Default Disabled
TEST / RESET button:
Serves for control of TEST, RESET, RESTART, HUSH, DIAGNOSTICS mode and INPUT DELAY set (without PC tool)
Temp. :
-10
o
C to +55
o
C
Humidity:
95%RH (No condensation)
Size (without ext. Antenna):
85 mm x 85 mm x 43 mm
Содержание UWI-IQ