18
EFFICIENCY CURVE
Efficiency curve guidance
Any pump setting will have a proper efficiency curve (Q / H curve). The AUTO (auto-adaptation) mode covers the
efficiency scope. The input power curve (P1 curve) belongs to each Q/H curve. The power curve represents the
pump power consumption (P1) in Watt for the given Q/H curve.
Conditions to obtain the curve
The description below regards efficiency curves for MAGI series pumps:
•
Pumped medium: water without gas.
•
The water density for which the curves were created was ρ= 983.2 kg / m3, temperature: + 60 °
•
All values expressed with curves are means, they cannot be treated as guaranteed curves. If a specific
efficiency is required, carry out a separate measurement for the given pump.
•
The curves were created using pumped water kinematic viscosity
υ
= 0,474 mm2 / s (0,474CcST)
BETA 2 25-60/180
BETA 2 25-60/130
BETA 2 25-40/180
The reference criterion for the most energy-efficient circulators is EEI ≤ 0.20. For the BETA 2 pump, EEI≤0.23,
this means that the BETA pump is an energy-saving pump
TECHNICAL DATA AND INSTALLATION DIMENSIONS
Ambient temperature
[ ]
C
Heating medium temperature
Minimum [ ]
C
Maxsimum [ ]
C
In order to protect the control panel and the pump stator against water steam condensation, always keep the temperature of the
heating medium higher than the ambient temperature.
0
2
95
10
10
95
20
20
95
30
30
95
35
35
90
40
40
70
Power supply
1×230V +6%/-10%
,
50Hz
,
PE
Motor protection
There is no need for additional motor protection
Protection rating
IP 44
Insulation class
Maximum relative humidity
Maximum pressure in the central heating system
Minimum inflow pressure at suction depending
on heating medium temperature
Acoustic pressure of working pump
Permissible ambient temperature
Maximum heating medium temperature
Maximum heating up of pump surface
Range of temperatures of pumped liquid
F
≤ 95%
IP 44
Medium temperature
Minimum inflow pressure
0.005 MPa
≤ 85 C
0.028 MPa
≤ 90 C
0.050 MPa
≤ 95 C
43 dB (A)
0
~
+40
℃
Tf95
≤ 110
℃
2
~
+95
℃
USE AND CARE GUIDE BETA 2
[ ]
C