Switch off the pump should be performed in this order:
First
the pump must be disconnected, and then the aggregate can be switched off. Switching
off the aggregate with a connected pump can result in pump motor getting burnt. In such a
case, only paid repair is available.
STORAGE:
The cleaned pump must be stored in a dry room.
Attention must be paid so that the whole length of the pump is placed on an even surface.
Supporting pump in one or more points can lead to pump deflection which can result in failure.
DEVICE DISPOSAL:
the used product is subject to disposal as wastes only in selective waste
collection systems organised by the Network of Communal Electric and
Electronic Waste Collection Centres. the customer is entitled to return the used
equipment to the network of the electric equipment distributor, at least for free
and directly, if the returned device is of proper type and fulfils the same function
as a newly purchased device.
EC DECLARATION OF CONFORMITY (Module A):
PHU DAMBAT address: Gawartowa Wola 38, 05-085 KAMPINOS
Under the Act of 30 August 2002 on the conformity system (Journal of Laws of 2004, No. 204 item 2087) we
declare with full responsibility that pumps included in the series 3SDm, 3SD, 3ti, 3t2i, 3SKm, 4SKm, 4SCR,
4SD, 4SDm, 3,5”SCM, 3,5”SCR, 90MSC, 4SKt, 3SQIBO, DWP, STING, SPm, SP, 3”SCR, 4ISP,6ISP.4ISPM,
FL, OLA, STm to which this declaration refers to are consistent with the following guidelines of the Council
on legal regulations unification in member states of EC:
1) MD 2006/42/EC (applied standards EN 292-1:1991, EN 292-2-1991/A1: 1995, PN-
EN 809:1999/AC: 2004)
2) EMC 2004/108/EC (applied standards PN-EN 55014-1:2004, PN-EN 61000-3-2:2004)
3) LVD 2014/35/EU (applied standards, PN EN 60335-1:2012, PN EN 60335-2-41:2012)
Adam Jastrzębski
02.10.2017
POSSIBLE OPERATION PROBLEMS AND TROUBLESHOOTING
Sign:
Possible cause:
Problem solution:
The pump does not
operate
Security device protecting
against
dry
operation
triggered
Wait until the water amount in the well is sufficient for
automatic pump launch.
Overcurrent security device
triggered
Check if there is an overload. Remove the cause. Wait until
the motor cools down and switch on the pump by means of
the switch built in the protecting cable box.
6
PUMP MATCHING WITH POWER GENERATOR:
The power of the rated current of the power generator, due to its high starting
current, should be 3 to 5 times higher than the rated current power of the supplied
motor.
On pump launch the following rule must be observed: the pump can only be
connected upon the power generator launch. If the aggregate is switched on with a
connected pump, it can lead to burning of the pump motor. in such a case, only
paid repair is available.