Chapter 3. Physical requirements
Physical requirements for installing the IBM XIV Storage System include:
v
“Cooling and environmental considerations”
v
“Physical space requirements” on page 11
v
“Raised floor requirements” on page 13
v
“Floor weight-support requirements” on page 14
v
“Physical network connection requirements” on page 14
v
“Delivery requirements” on page 14
Cooling and environmental considerations
Cooling requirements
Cooling (thermal dissipation) requirements are shown in Table 7.
Table 7. Thermal dissipation - partial and full rack configurations
Rack configuration
Number of modules (See Note
1.)
kBTU per hour
Full
15
28.5
Partial (See Note 2.)
14
26.6
13
24.7
12
22.8
11
20.8
10
18.9
9
17.0
6
11.7
Notes:
1.
Seven (7) and eight (8) module configurations are not supported.
2.
Thermal dissipation for partial rack configurations are typical values and are provided
for reference purposes only. To support concurrent capacity upgrades, the client’s site
must provide cooling arrangements to support a full rack configuration.
Air circulation
v
Cold air is provided from the front of the rack.
v
Hot air is exhausted from the back of the rack.
Airflow
Airflow requirements are shown in Table 8.
Table 8. Airflow requirements - partial and full rack configurations
Rack configuration
Number of modules (See
Note 1.)
Cubic feet per minute
(CFM)
Full
15
810
© Copyright IBM Corp. 2008, 2009
9
||
|
|
||
|||
|||
||
||
||
||
||
||
|
|
|
|
|
|
||
|
|
|
|
|
|||
Содержание XIV STORAGE SYSTEM
Страница 2: ......
Страница 6: ...iv IBM XIV Storage System Introduction and Planning Guide...
Страница 8: ...vi IBM XIV Storage System Introduction and Planning Guide...
Страница 10: ...viii IBM XIV Storage System Introduction and Planning Guide...
Страница 22: ...2 IBM XIV Storage System Introduction and Planning Guide...
Страница 28: ...8 IBM XIV Storage System Introduction and Planning Guide...
Страница 36: ...16 IBM XIV Storage System Introduction and Planning Guide...
Страница 42: ...22 IBM XIV Storage System Introduction and Planning Guide...
Страница 46: ...26 IBM XIV Storage System Introduction and Planning Guide...
Страница 51: ...Acoustic output __ v Sound power LwAu 8 4 bels Appendix D Specifications pre August 2009 racks 31...
Страница 52: ...32 IBM XIV Storage System Introduction and Planning Guide...
Страница 61: ......
Страница 62: ...U S A GA52 1327 07...