Chapter 4. Cabling the PDU
This chapter provides information about connecting the PDU to a power source
and about connecting devices.
Connecting input power
The PDU is a high-voltage dc device that must be connected to its input power
source by a Licensed Electrician.
L015
DANGER:
Arc Flash/Arc Blast hazard when disconnected with power on. Turn off power before
disconnecting. (L015)
Attention:
You are responsible for making sure that only a Licensed Electrician
installs or removes the PDU power cable from the DC Power source. All National
and Local building code requirements must be met. IBM service technicians are not
Licensed Electricians.
The PDU input power cable is 4.3 m (14.1 ft.) in length, with a pig-tail termination.
It has three stranded copper conductors, each with a cross section of 25 sq. mm
(approximately 2 AWG).
The PDU requires a high-voltage dc power source between 240 V dc and 380 V dc
with 90 A capacity that is protected by a 100 A circuit breaker.
The PDU conductors are connected to a high-voltage dc power source of as
described in the table. All connections must be performed by a licensed electrician,
following local electrical codes or requirements.
Table 2. PDU input cable connection
Wire color
Function
Green-yellow
Earth ground
Blue
Negative dc voltage
Brown
Positive dc voltage
Connecting output devices
The PDU power outlets are for connecting high-voltage dc devices. Connect a
device to a power outlet on the PDU with the power cord that comes with the
device. See the documentation that comes with your high-voltage dc device for
information and instructions.
© Copyright IBM Corp. 2014
23
Содержание System X High Voltage DC PDU
Страница 1: ...1U Higher Voltage DC PDU 240V 380V Installation and Maintenance Guide...
Страница 2: ......
Страница 3: ...1U Higher Voltage DC PDU 240V 380V Installation and Maintenance Guide...
Страница 6: ...iv 1U Higher Voltage DC PDU 240V 380V Installation and Maintenance Guide...
Страница 26: ...16 1U Higher Voltage DC PDU 240V 380V Installation and Maintenance Guide...
Страница 32: ...22 1U Higher Voltage DC PDU 240V 380V Installation and Maintenance Guide...
Страница 34: ...24 1U Higher Voltage DC PDU 240V 380V Installation and Maintenance Guide...
Страница 36: ...26 1U Higher Voltage DC PDU 240V 380V Installation and Maintenance Guide...
Страница 38: ...28 1U Higher Voltage DC PDU 240V 380V Installation and Maintenance Guide...
Страница 42: ...32 1U Higher Voltage DC PDU 240V 380V Installation and Maintenance Guide...
Страница 50: ...40 1U Higher Voltage DC PDU 240V 380V Installation and Maintenance Guide...
Страница 52: ...42 1U Higher Voltage DC PDU 240V 380V Installation and Maintenance Guide...
Страница 53: ......
Страница 54: ...Part Number 16Y6043 Printed in USA 1P P N 16Y6043...