Table 7. DC power supply LED indicators (continued)
Name
Label
Color
State
Description
Fault
Amber
OFF
No fault detected.
ON
PSU fault was detected.
BLINK
PSU is being identified. A
fault might have been
detected.
(None)
Blue
N/A
Not used.
Connecting a DC power supply to a DC power source
An enclosure that is DC powered contains two DC power supply units (PSUs). Each unit must be
connected to a suitable -48V DC power source. To provide redundancy in a power circuit failure, connect
the two PSUs to different DC power sources.
Note: The connection to the DC power source must be made by trained service personnel. Ensure that the
connection is made in accordance with all the requirements of the equipment that is being used.
Use the supplied cables to connect the DC PSUs to the power sources. Use only the IBM supplied DC
power cable (IBM part number 00AR087) to connect the unit to a DC power source.
The supplied power must meet the input requirements that are listed in Table 8 on page 12.
Table 8. DC power supply input requirements
Requirement
Min
Max
Voltage (V DC)
-48
-60
Instantaneous (V DC for < 1 second)
-36
-75
Inrush current at initial turn on (-48V DC)
34 A
Out of spec time before power off is signaled
5 ms
Important: Each PSU cable must be protected by a 20A circuit breaker. These instructions assume that
the circuit breaker is separate from the DC power distribution unit. Refer to the DC power distribution unit
documentation and the circuit breaker documentation for details. Follow the instructions that are given
there for connecting the circuit breaker to the power distribution unit and for connecting the DC power
cable to the circuit breaker.
One end of the cable ends in a plug that fits the DC PSU. At the other end of the cable, each individual wire
ends with a 6 mm diameter ring terminal that is designed to fit an M6 stud. Provide adequate strain relief
after you attach the ring terminals to the power source. Table 9 on page 12 lists the wire colors.
If it is necessary to replace the ring terminals with a different connector, choose a suitably sized and rated
UL-listed connector that is appropriate for the wire gauge and available current. Install the ring terminals
according to the instructions provided by the manufacturer.
Table 9. DC cable wire color coding
Color
Function
Blue
Return
Green / Yellow
Ground
Brown
-48V
12 Storwize V5000 Gen2: Quick Installation Guide
Содержание Storwize V5000 Gen2
Страница 1: ...IBM Storwize V5000 Gen2 Quick Installation Guide IBM...
Страница 5: ...Index 149 v...
Страница 6: ...vi...
Страница 156: ...130 Storwize V5000 Gen2 Quick Installation Guide...
Страница 164: ...138 Storwize V5000 Gen2 Quick Installation Guide...
Страница 166: ...140 Storwize V5000 Gen2 Quick Installation Guide...
Страница 168: ...142 Storwize V5000 Gen2 Quick Installation Guide...
Страница 177: ......
Страница 178: ...IBM...