The switch card contains two separate switches:
FC-AL Address switch
«5¬
This switch can be set to a value between 0 and 7. It controls the FC-AL
addresses used by the ProFibre Storage Array. For example, if the switch is
set to 5, the FC-AL address of the disks in slots 1 to 10 are then 50 to 59
(hexadecimal). In this case, the address of the enclosure services is 5A
(hexadecimal).
Note:
Each enclosure in the ProFibre Storage Array must have a unique
switch setting. Switch settings of 8 or 9 are not supported and
should not be used; however, if selected are treated as 7. If switch
card settings 7, 8, and 9 are used in the same system, unique FC-AL
addresses cannot be assigned to the disk drive slots.
Below the FC-AL Address switch is a 4-bit dip switch called the option switch.
Option Switch
v
Switch 1—Orientation Switch:
«1¬
This switch should be set to ON
indicating a rack-mounted unit.
v
Switch 2 — Not used
«2¬
: This switch should be set OFF.
v
Switch 3 — Not used
«3¬
: This switch should be set OFF.
v
Switch 4 — Not used
«4¬
: This switch should be set OFF.
Figure 11. Switch Card (with or without BBU)
10
ProFibre Storage Array: Operator’s Guide
Содержание StorageSmart DF1100J
Страница 2: ......
Страница 6: ...iv ProFibre Storage Array Operator s Guide...
Страница 22: ...12 ProFibre Storage Array Operator s Guide...
Страница 40: ...30 ProFibre Storage Array Operator s Guide...
Страница 42: ...32 ProFibre Storage Array Operator s Guide...
Страница 46: ...36 ProFibre Storage Array Operator s Guide...
Страница 48: ...38 ProFibre Storage Array Operator s Guide...
Страница 51: ......