Chapter 2. Installing and configuring the SAN06B-R
You can install the SAN06B-R in the following ways:
v
As a stand-alone unit on a flat surface. For instructions and more information,
see “Setting up the switch as a standalone unit” on page 8.
v
In an Electronic Industries Association (EIA) cabinet using the fixed rack mount
kit, slide rack mount kit, or the mid-mount rack kit. For more information, see
“Installing in an EIA cabinet” on page 9.
To install and operate the switch successfully, ensure that the following
requirements are met:
v
The primary AC input is 100-240 VAC (switch autosenses input voltage), 47-63
Hz. 200-240 VAC is recommended.
v
The primary outlet is correctly wired, protected by a circuit breaker, and
grounded in accordance with local electrical codes.
v
The supply circuit, line fusing, and wire size are adequate, as specified by the
electrical rating on the switch nameplate.
For power supply information, see “Power supply” on page 38.
To ensure adequate cooling, install the switch with the nonport side, which
contains the air intake vents, facing a cool-air aisle.
Verify that the ambient air temperature does not exceed 40° C (104° F) and that the
ambient humidity remains between 20% and 85% while the switch is operating.
This chapter provides the following information:
v
“Items included with the switch”
v
“Installation and safety considerations” on page 8
v
“Setting up the switch as a standalone unit” on page 8
v
“Installing in an EIA cabinet” on page 9
v
“Cabling and setting up the switch” on page 14
v
“Managing license keys (optional)” on page 23
Items included with the switch
The following items are included with the standard shipment of the switch. When
you open the packaging, verify that these items are included in the package and
that no damage occurred during shipping.
Note:
If any items are damaged or missing, within the United States and Canada,
contact the IBM Quality Hotline toll-free 1-800-442-6773 or direct dial in
other locations: 770-858-8459.
v
The SAN06B-R switch, containing two combined power supply/fan assembly
FRUs
v
The following rack mount kits are optionally available:
– Fixed rack mount kit, with installation instructions
– Slide rack mount kit, with installation instructions
– Mid-mount kit, with installation instructions
© Copyright IBM Corp. 2009, 2013
7
Содержание SAN06B-R
Страница 2: ......
Страница 8: ...vi SAN06B R Installation Service and User Guide...
Страница 12: ...x SAN06B R Installation Service and User Guide...
Страница 14: ...xii SAN06B R Installation Service and User Guide...
Страница 24: ...xxii SAN06B R Installation Service and User Guide...
Страница 32: ...6 SAN06B R Installation Service and User Guide...
Страница 62: ...36 SAN06B R Installation Service and User Guide...
Страница 68: ...42 SAN06B R Installation Service and User Guide...
Страница 80: ...54 SAN06B R Installation Service and User Guide...
Страница 83: ......
Страница 84: ...Part Number 98Y5370 Printed in USA GC27 2270 02 1P P N 98Y5370...