Attaching the Rack to a Short-Raised or Long-Raised Floor
Attention:
It is the customer’s responsibility to ensure the following steps are completed before the
service representative performs the tie-down procedure.
Note:
To accommodate a floor with a depth of more than 16 inches, a steel beam or a steel channel
adapter for mounting the subfloor eyebolts is required. The customer must supply the floor eyebolts.
Consider the following when preparing the floor for tie-down:
v
The hardware is designed to support a frame weighing no more than 2636 pounds.
v
The estimated maximum concentrated load on one caster for a 2636-pound system is 900 pounds. For
a multiple system installation, it is possible that one floor tile will bear a total concentrated load of 1800
pounds.
To install the eyebolts, do the following:
1. Obtain the service of a qualified structural engineer to determine the appropriate installation of the
eyebolts.
2. Consider the following before installing the eyebolts:
v
Floor eyebolts must be securely anchored to the concrete floor.
v
The minimum height of the center of the internal diameter is 1 inch above the concrete floor surface.
v
The maximum height is 2.5 inches above the concrete floor surface. Higher than 2.5 inches can
cause excessive lateral deflection to the tie-down hardware.
v
The eyebolt’s internal diameter should be 1-3/16 inch, and each eyebolt should be able to withstand
2700 pounds. The customer should obtain the service of a qualified consultant or structural engineer
to determine the appropriate anchoring method for these eyebolts and to ensure that the raised floor
can support the floor-loading specifications provided in the
Site and Hardware Planning Information
,
order number SA38-0508.
48
Eserver
pSeries 670 Installation Guide
Содержание pSeries 670
Страница 1: ...pSeries 670 Installation Guide SA38 0613 02 ERserver...
Страница 2: ......
Страница 3: ...pSeries 670 Installation Guide SA38 0613 02 ERserver...
Страница 8: ...vi Eserver pSeries 670 Installation Guide...
Страница 12: ...x Eserver pSeries 670 Installation Guide...
Страница 14: ...xii Eserver pSeries 670 Installation Guide...
Страница 22: ...6 Eserver pSeries 670 Installation Guide...
Страница 42: ...26 Eserver pSeries 670 Installation Guide...
Страница 52: ...36 Eserver pSeries 670 Installation Guide...
Страница 56: ...40 Eserver pSeries 670 Installation Guide...
Страница 78: ...62 Eserver pSeries 670 Installation Guide...
Страница 84: ...68 Eserver pSeries 670 Installation Guide...
Страница 96: ...80 Eserver pSeries 670 Installation Guide...
Страница 104: ...88 Eserver pSeries 670 Installation Guide...
Страница 124: ...108 Eserver pSeries 670 Installation Guide...
Страница 127: ......
Страница 128: ...Part Number 00P5809 Printed in U S A May 2003 SA38 0613 02 1P P N 00P5809...