About this task
Important:
You can accomplish most service actions when the node is fully extended from the
rack on its slide rails.
To remove an AC2 enclosure from the rack, complete these steps:
Note:
Make sure that you have two people when you lift the server; position their
hands as shown in Figure 1.
Procedure
1.
Pull back the cable-management arm if you are working from the rear of the
rack, or slide the node out of the rack to the fully extended rail position if you
are working from the front.
2.
Disconnect and label all cable connections to the enclosure back panel.
3.
Pull the locking levers
▌1▐
forward, as shown in Figure 1.
4.
Support the rear of the server, and lift the front of the server up slightly
▌2▐
to
clear the nailhead
▌3▐
from the slot.
5.
Lift the rear
▌1▐
of the server to level the server after the front nailheads clear
the latches, as shown in the following figure.
6.
Lift the server out of the rack
▌2▐
and place it on a sturdy surface.
1
Lift point
Lift point
2
3
Figure 1. Removing the AC2 from the rack
4
FlashCore Forever: Hardware Installation Guide
Содержание FlashSystem 9150
Страница 1: ...FlashCore Forever Hardware Installation Guide IBM...
Страница 4: ...iv FlashCore Forever Hardware Installation Guide...
Страница 10: ...6 FlashCore Forever Hardware Installation Guide...
Страница 12: ...4 Rack Rear Figure 4 Removing the rear end of the slide rails 8 FlashCore Forever Hardware Installation Guide...
Страница 22: ...18 FlashCore Forever Hardware Installation Guide...
Страница 26: ...22 FlashCore Forever Hardware Installation Guide...
Страница 27: ......
Страница 28: ...IBM Printed in USA...