Table 6-1. Troubleshooting (continued)
Problem indicator
Component
Possible cause
Possible solutions
All green LEDs are off
All components
Subsystem power is off
Make sure that all storage subsystem
power cables are connected and that the
power-supply switches are on. If
applicable, make sure that the main circuit
breakers for the rack are turned on.
Power failure
Check the main circuit breaker and ac
receptacle (ac models). Check the -48 V dc
power source and disconnect device (dc
models).
Power-supply failure
Replace the power supply.
Operating environment is
too hot
Cool down the environment.
Amber LED is flashing
Drives (fault LED is
lit)
Drive identification is in
process
No corrective action is needed.
One or more green
LEDs are off
Power supplies
Power cable is
disconnected or switches
are turned off
Make sure that the power cables are
connected (ac or dc) and that the
disconnect device (dc only) and the
power-supply switches are turned on.
All drives
Midplane failure
Replace the DS3500. Contact your IBM
technical-support representative.
Several components Hardware failure
Replace the affected components. If this
does not correct the problem, replace the
controllers. Contact your IBM
technical-support representative.
The DS3500 was not
powered-on, or all SAS
cable connections
between the storage
enclosures and the
DS3500 storage
subsystem failed.
Perform one of the following actions:
v
Power-on the storage subsystem.
v
Make sure that the SAS cable
connections between the storage
enclosures and the DS3500 storage
subsystem are made.
Front panel
Power supply problem
Make sure that the power cables are
connected and that the power supplies are
turned on.
Hardware failure
If any other LEDs are lit, replace the
midplane. Contact your IBM
technical-support representative.
Green LED is flashing
slowly (once every 2
seconds)
Drives
The DS3500 was not
powered-on, or all SAS
connections between the
storage enclosures and
the DS3500 storage
subsystem have failed.
Perform one of the following actions:
v
Power-on the storage subsystem.
v
Make sure that the SAS connections
between the storage enclosures and the
DS3500 storage subsystem are made.
v
Make sure that all the storage
enclosures in the same channel pair
have the same enclosure speed setting.
6-4
System Storage DS3500 and EXP3500: Installation, User's, and Maintenance Guide
Содержание DS3500
Страница 1: ...System Storage DS3500 and EXP3500 Installation User s and Maintenance Guide GA32 0952 01...
Страница 5: ...Index X 1 Contents v...
Страница 6: ...vi System Storage DS3500 and EXP3500 Installation User s and Maintenance Guide...
Страница 10: ...x System Storage DS3500 and EXP3500 Installation User s and Maintenance Guide...
Страница 44: ...2 6 System Storage DS3500 and EXP3500 Installation User s and Maintenance Guide...
Страница 94: ...3 50 System Storage DS3500 and EXP3500 Installation User s and Maintenance Guide...
Страница 116: ...4 22 System Storage DS3500 and EXP3500 Installation User s and Maintenance Guide...
Страница 164: ...6 8 System Storage DS3500 and EXP3500 Installation User s and Maintenance Guide...
Страница 174: ...A 4 System Storage DS3500 and EXP3500 Installation User s and Maintenance Guide...
Страница 178: ...B 4 System Storage DS3500 and EXP3500 Installation User s and Maintenance Guide...
Страница 185: ...People s Republic of China Class A electronic emission statement Taiwan Class A compliance statement Notices C 7...
Страница 186: ...C 8 System Storage DS3500 and EXP3500 Installation User s and Maintenance Guide...
Страница 190: ...X 4 System Storage DS3500 and EXP3500 Installation User s and Maintenance Guide...
Страница 191: ......
Страница 192: ...Part Number 90Y8716 Printed in USA GA32 0952 01 1P P N 90Y8716...
Страница 193: ...Click below to find more Mipaper at www lcis com tw Mipaper at www lcis com tw...