Follow the suggested actions in the order in which they are listed in the Action column until the problem
is solved.
v
See Chapter 3, “Parts listing,” on page 23 to determine which components are CRUs and which
components are FRUs.
v
If an action step is preceded by “(Trained service technician only),” that step must be performed only by a
trained service technician.
Symptom
Action
A blade server does not
power-on.
v
Press the power-control button on the blade server to turn it on. See your blade
server documentation for more information.
v
Reseat the blade server.
v
Make sure that power modules are installed and working.
Note:
Power modules 1 and 2 provide power to blade bays 1 through 6, and
power modules 3 and 4 supply power to blade bays 7 through 10.
v
Make sure that at least one management module is installed and it is active and
working.
v
Check the event log, using the management-module Web interface.
v
Use the management-module Web interface to make sure that local power
control is enabled for the blade server.
v
Make sure that the fault LEDs on the multiplexer expansion modules are not lit.
If a fault LED on a multiplexer expansion module is lit, reseat the module.
v
Move the blade server to a known working bay in the BladeCenter HT unit or in
another BladeCenter HT unit.
v
Replace the blade server.
Fan-module problems
v
Follow the suggested actions in the order in which they are listed in the Action column until the problem
is solved.
v
See Chapter 3, “Parts listing,” on page 23 to determine which components are CRUs and which
components are FRUs.
v
If an action step is preceded by “(Trained service technician only),” that step must be performed only by a
trained service technician.
Symptom
Action
A fan module is running at full
speed.
1. Make sure that:
v
All other fan modules are installed and working.
v
At least one management module is installed and it is active and working.
2. Reseat the following components:
a. Multiplexer expansion modules (see “Removing a multiplexer expansion
b. Fan modules (see “Removing a fan module” on page 83)
3. Reverse the locations of the fan modules. (If more than two fan modules are
removed or more than two fan modules experience a double fan failure, the
blade servers will shut down within 1 to 3 seconds.)
a. If the same fan module runs at full speed, replace it.
b. If a different fan module in the same bay runs at full speed, call for service.
Chapter 5. Diagnostics
103
Содержание BladeCenter HT 8740
Страница 1: ...BladeCenter HT Type 8740 and 8750 Problem Determination and Service Guide ...
Страница 2: ......
Страница 3: ...BladeCenter HT Type 8740 and 8750 Problem Determination and Service Guide ...
Страница 8: ...vi BladeCenter HT Type 8740 and 8750 Problem Determination and Service Guide ...
Страница 48: ...30 BladeCenter HT Type 8740 and 8750 Problem Determination and Service Guide ...
Страница 118: ...100 BladeCenter HT Type 8740 and 8750 Problem Determination and Service Guide ...
Страница 142: ...124 BladeCenter HT Type 8740 and 8750 Problem Determination and Service Guide ...
Страница 150: ...132 BladeCenter HT Type 8740 and 8750 Problem Determination and Service Guide ...
Страница 156: ...138 BladeCenter HT Type 8740 and 8750 Problem Determination and Service Guide ...
Страница 157: ......
Страница 158: ... Part Number 00V9904 Printed in USA 1P P N 00V9904 ...