![IBM 88861TU Скачать руководство пользователя страница 41](http://html2.mh-extra.com/html/ibm/88861tu/88861tu_planning-manual_3296880041.webp)
Four power supplies attached to 220 V ac power sources
In this example, there are four power supplies that are attached to two separate
power sources.
v
Power source A could be your utility provider
v
Power source B could be your UPS service
Power
module 3
Power
module 4
Power
module 1
Power
module 2
!
!
!
!
Power
source A
Power
source A
Power
source B
Power
source B
Each power supply provides up to 1450 watts. Therefore, the total power available
for the BladeCenter S system would be as follows:
v
Non-redundant power policy: 3562 watts
v
AC power source redundancy power policy: 2900 watts
Cooling considerations
The operating environment for BladeCenter S systems must provide sufficient
temperature and humidity control to prevent BladeCenter S system thermal
failures.
Air temperature and humidity
Temperature and humidity limits exist for a BladeCenter S system.
The following table describes the permissible temperatures and humidity limits for
a BladeCenter S system when it is powered on.
Table 8. Temperature and humidity limits
Altitude
Temperature Range
Humidity Range
0 to 914 m (0 to 3,000 ft)
10° to 35° C (50° to 95° F)
8% to 80%
914 m to 2134 m (3,000 ft to
7,000 ft)
10° to 32° C (50° to 90° F)
8% to 80%
Chapter 2. Planning for the physical environment
35
Содержание 88861TU
Страница 1: ...IBM BladeCenter S Type 7779 8886 Planning Guide...
Страница 2: ......
Страница 3: ...IBM BladeCenter S Type 7779 8886 Planning Guide...
Страница 30: ...24 BladeCenter S Type 7779 8886 Planning Guide...
Страница 44: ...38 BladeCenter S Type 7779 8886 Planning Guide...
Страница 76: ...70 BladeCenter S Type 7779 8886 Planning Guide...
Страница 110: ...Volume name Size in GB Hosts blade servers Applications 104 BladeCenter S Type 7779 8886 Planning Guide...
Страница 118: ...112 BladeCenter S Type 7779 8886 Planning Guide...
Страница 123: ...Chinese Class A warning statement Japanese Voluntary Control Council for Interference FCS statement Notices 117...
Страница 124: ...118 BladeCenter S Type 7779 8886 Planning Guide...
Страница 128: ...122 BladeCenter S Type 7779 8886 Planning Guide...
Страница 129: ......
Страница 130: ...Part Number 60Y1614 Printed in USA 1P P N 60Y1614...