Figure 30. Removing the cable channel cover
Item
Description
Item
Description
1
Cable channel cover retaining
screw
5
Shield
2
Cable channel cover
6
Power distribution panel
3
Power distribution panel top
cover retaining screws
4
Power distribution panel top
cover
3. Remove the -48 V DC bus bar shield from the power distribution panel.
DANGER: The bus bar shield must be correctly reinstalled over the -48 V DC return bus bars to
protect against injury while servicing the power distribution panel.
4. Ensure that the following steps are performed when connecting the DC power source.
a. At -48 V DC power source, turn off any -48 V DC power sources that will be connected to the power
distribution panel.
b. After the -48 V DC power sources are turned off, be sure there is a tag or label over the power
source switches or fuses (lock-out/tag-out) to indicate that the power source is turned off
intentionally.
Note: Ensure that any oxidation on the copper bus bars is removed.
c. If this is a raised-floor installation and you are working at the rear of the rack, route the power
cables up the rack's right side.
d. Ensure that the external -48 V DC power cable is connected correctly to the -48 V DC bus bar.
Racks and rack features 45
Содержание 7014 T00
Страница 1: ...Power Systems Racks and rack features IBM ...
Страница 4: ...iv ...
Страница 14: ...xiv Power Systems Racks and rack features ...
Страница 149: ...Figure 96 Fastening the rack braces 5 Remove the four corner screws from the top cover Racks and rack features 135 ...
Страница 151: ...Figure 98 Removing the remaining screws 7 Lift off the top cover Racks and rack features 137 ...
Страница 167: ...Figure 110 Installing the inner hose panel Racks and rack features 153 ...
Страница 184: ...170 Power Systems Racks and rack features ...
Страница 195: ......
Страница 196: ...IBM ...