14
6: O
UTPUT
V
OLTAGE
S
ELECTION
Terminal Mode is a menu driven interface that enables enhanced configuration of the uninterruptible power supply through a serial
connection.
Connect the serial cable to the serial port on the rear side of the uninterruptible power supply.
1.
When using the PowerChute
®
Business Edition or Network Shutdown software, stop the PowerChute Business Edition agent and
server services
using the following steps:
a. From the desktop, click
Start
=>
Settings
=>
Control Panel
=>
Administrative Tools
=>
Services
.
b. Select
PCBE Server
and
PCBE Agent
or
APC PBE Agent
, then, right click the mouse and select
Stop
.
2.
The Network Management Card (NMC) is factory installed in the IBM 5000XHV SmartSlot located on the rear panel. The NMC
must be removed from the SmartSlot prior to uninterruptible power supply terminal mode configuration.
Remove the two screws that secure the NMC to the uninterruptible power supply chassis. Carefully remove the NMC.
3.
Open a terminal program, for example HyperTerminal.
From the desktop, click
Start
=>
Programs
=>
Accessories
=>
Communication
=>
HyperTerminal.
4.
Double-click on the
HyperTerminal
icon.
a. Follow the prompts to choose a name and select an icon. Disregard the message,
must install a modem
, if it is displayed. Click
OK
.
b. Select the
COM
port that is connected to the uninterruptible power supply. The port settings are:
9
bits per second - 9600
9
data - bits 8
9
parity - none
9
stop bit - 1
9
flow control - none
c. Click Enter.
5.
Once the blank terminal window is open, follow these steps to configure the output voltage:
a. Press
Enter
to initiate terminal mode.
b. Press
1
to select uninterruptible power supply
Settings
. Wait for the uninterruptible power supply
Settings
menu to appear on
the screen.
c. Press
1
to select
Output Voltage
.
d. Select the number corresponding to the desired voltage setting, then press
Y
to confirm.
f. Press
Esc
multiple times until logged out.
6.
Reinstall the NMC using the two screws previously removed.
7.
Start the PowerChute Business Edition agent and server services
using the following steps:
a. From the desktop, click
Start
=>
Settings
=>
Control Panel
=>
Administrative Tools
=>
Services
.
b. Select
PCBE Server
and
PCBE Agent
or
APC PBE Agent
; then, right click the mouse and select
Start
.
©
Copyright International Business Machines Corporation 2009. All rights reserved.
U.S. Government Users – Restricted rights –
Use, duplication or disclosure is subject to restrictions set forth in GSA ADP Schedule Contract with IBM Corp.
Trademarks
IBM is trademark of International Business Machines Corporation in the United States, other countries, or both. APC and PowerChute are registered
trademarks of American Power Conversion Corporation. Microsoft, Windows, Windows Me, Windows NT, and Windows XP are trademarks of Microsoft
Corporation in the United States, other countries, or both. Other company, product, or service names may be trademarks or service marks of others.