Table 12. 1500 VA LCD tower uninterruptible power supply CRU listing
Description
MTM
CRU part number (Tier 1)
Uninterruptible power supply chassis
1500 VA tower (100 V)
5396-2JX
69Y6086
Uninterruptible power supply chassis
1500 VA tower (120 V)
5396-2AX
69Y6082
Uninterruptible power supply chassis
1500 VA tower (230 V)
5396-2KX
69Y6087
Battery module
5396-2AX, 5396-2JX, 5396-2KX
69Y6079
Bezel, front
5396-2AX, 5396-2JX, 5396-2KX
69Y6078
USB cable
69Y6073
RS-232 cable
69Y6074
Remote emergency power-on (REPO) switch
69Y6075
Environmental monitoring probe kit
41Y9210
Network management card
46M4112
Network management card setup cable (serial
communication cable)
81Y2372
Power cord, 13 A / 125 V, 2.8 m, NEMA 5-15P to
IEC 320 C13
5396-2AX
39M5512
Power cord, 18 A / 125 V, 2.5 m, NEMA 5-20P to
IEC 320 C19
5396-2JX
39M5306
Uninterruptible power supply and battery care
For the best preventive maintenance, keep the area around the uninterruptible
power supply clean and dust-free. If the atmosphere is very dusty, clean the outside
of the system with a vacuum cleaner. For full battery life, keep the uninterruptible
power supply at an ambient temperature of 25°C (77°F).
Storing the uninterruptible power supply and batteries
If you store the uninterruptible power supply for a long period, recharge the battery
every 6 months by connecting the uninterruptible power supply to a power outlet.
The batteries charge to 90% capacity in approximately 4 hours. However, you
should charge the batteries for 48 hours after long-term storage. Check the battery
recharge date on the shipping carton label. If the expiration date has passed and
the batteries were never recharged, do not use the uninterruptible power supply.
Contact your technical-support representative.
Replacing the battery module (qualified personnel only)
CAUTION:
Lead-acid batteries can present a risk of electrical burn from high,
short-circuit current. Avoid battery contact with metal materials; remove
watches, rings, or other metal objects, and use tools with insulated handles.
To avoid possible explosion, do not burn.
Exchange only with the IBM-approved part. Recycle or discard the battery as
instructed by local regulations. In the United States, IBM has a process for
the collection of this battery. For information, call 1-800-426-4333. Have the
IBM part number for the battery unit available when you call. (C004)
34
1000 VA and 1500 VA LCD Tower UPS: Installation and Maintenance Guide
Содержание 1000VA
Страница 1: ...1000 VA LCD Tower UPS and 1500 VA LCD Tower UPS Installation and Maintenance Guide...
Страница 2: ......
Страница 3: ...1000 VA LCD Tower UPS and 1500 VA LCD Tower UPS Installation and Maintenance Guide...
Страница 50: ...40 1000 VA and 1500 VA LCD Tower UPS Installation and Maintenance Guide...
Страница 67: ......
Страница 68: ...Part Number 60Y1421 Printed in USA 1P P N 60Y1421...