Address Name
Designation
Data
form
Read/
Write
Factor Unit
1
Reset alarm
Write 1 for resetting the alarm.
Single bit Read/
Write
2
Blow-cleaning
A Write on this address implies
that Modbus assumes control of
this function. Write 1 to activate
blow-clean function or 0 to
deactivate.
Single bit Read/
Write
3
Rotation monitor
Reads 1 if the rotation monitor
is active. A Write on this address
implies that Modbus assumes
control of this function. Write 1
to activate the rotation monitor
or 0 to deactivate.
Single bit Read/
Write
4
Manual speed
Write 1 to activate manual speed
instead of the control signal
from Modbus. If the function
is activated via the digital input
it cannot be deactivated via
Modbus.
Single bit Read/
Write
MODBUS REGISTRY FOLDER
COIL
VariMax25M supports the following Modbus functions:
◆ Coil (digital Read/Write)
◆ Discrete input (digital Read)
◆ Input registry (analogue Read)
◆ Holding registry (analogue Read/Write)
1-bit registry (Read/Write).
Modbus function 01 "Read Coil Status" is used for reading.
Modbus function 05 "Force Single Coil" is used for writing.
0 = not active
1 = active
19