Address Name
Designation
Data
form
Read/
Write
Factor Unit
1
Reset alarm
Write 1 for resetting the alarm.
Single bit Read/
Write
2
Cleaning function
Reads 1 if the cleaning function
is active. A Write on this address
implies that Modbus assumes
control of this function. Write 1
to activate cleaning function or
0 to deactivate.
Single bit Read/
Write
3
Rotation monitor
Reads 1 if the rotation monitor
is active. A Write on this address
implies that Modbus assumes
control of this function. Write 1
to activate the rotation monitor
or 0 to deactivate.
Single bit Read/
Write
4
Manual speed
Reads 1 if the manual speed
is active. Write 1 to activate
manual speed instead of the
control signal from Modbus.
If the function is activated via
the digital input it cannot be
deactivated via Modbus.
Single bit Read/
Write
MODBUS REGISTER FOLDER
COIL
VariMax50M supports the following Modbus functions:
◆ Coil (digital Read/Write)
◆ Discrete input (digital Read)
◆ Input register (analogue Read)
◆ Holding register (analogue Read/Write)
1-bit register (Read/Write).
Modbus function 01 "Read Coil Status" is used for reading.
Modbus function 05 "Force Single Coil" is used for writing.
0 = not active
1 = active