INSTALLATION AND OPERATION INSTRUCTIONS
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
3
SPECIFICATIONS
SPECIFICATION
VFC 15-150
VFC 45-225
CSA Input (Natural Gas or Propane) - MBH
CSA Input (Natural Gas or Propane) - kW
CSA Output - MBH
CSA Output - kW
15 - 150
4.4 - 44
14 - 139
4.1 - 41
45 - 225
13 - 66
41 - 206
12 - 60
A.F.U.E.
95%
95%
Minimum gas supply pressure (Natural Gas or
Propane) - inch w.c.
3
3
3
3
Maximum gas supply pressure (Natural Gas or
Propane) - inch w.c.
14
14
14
14
Power use (120Vac/60Hz) @ full fire - Watts
(excluding pumps)
57
167
Weight (shipping) - lbs/Kg
165 / 75
168 / 76
Pressure vessel water content - USG/Litres
2.4 / 9
2.4 / 9
Maximum boiler flow rate - USgpm
16
25
Minimum boiler flow rate - USgpm
4
8
Maximum operating water pressure* - psig
80
80
Minimum water pressure - psig
8
8
Normal flue temperature @ 100°F boiler return
water temperature - high fire
100 to 105 °F
37.8 to 40.5°C
100 to 105 °F
37.8 to 40.5°C
Normal flue temperature @ 160°F boiler return
water temperature - high fire
160 to 165 °F
71.1 to 73.9°C
160 to 165 °F
71.1 to 73.9°C
Approved installation altitude - ASL
0 - 12,000’
0 - 12,000’
Ambient temperature - Low (°F-°C)
Ambient temperature - High (°F-°C)
32°F / 0°C
122°F / 50°C
32°F / 0°C
122°F / 50°C
Max. relative humidity (non-condensing)
90%
90%
Minimum water temp.
34°F / 1.1°C
34°F / 1.1°C
Maximum water temp. (electronic hi-limit)
190°F / 87.8°C
190°F / 87.8°C
Maximum water temp. (mechanical hi-limit)
200°F / 93.3°C
200°F / 93.3°C
Max. ΔT - supply/return (electronic fence)
40°F
40°F
Maximum equivalent vent length
- 2”
Each side (Vent & Air Intake))
- 3”
(Natural Gas or Propane)
Air intake options: either direct vent or indoor
supply
50’
120’
N/A
240’
* boilers are shipped with 30 psig pressure relief valve