background image

INSTALLATION AND OPERATION INSTRUCTIONS

1-26

SL 30-175 MODULATING GAS BOILER

ELECTRICAL CONNECTIONS

All Electrical wiring to the boiler (including grounding) must conform to local 

electrical codes and/or National Electrical Code, ANS/NFPA No. 70 – latest 

edition, or The Canadian Electrical Code, C22.1 - Part 1.

1.8.1 120VAC Line Voltage Hook-up

Line-voltage wiring is done within the field-wiring box. 

(Refer to Section 

6.2.Wiring Diagram on page 6-4).

 Connect the boiler to the grid power using a 

separate, fused circuit and on/off switch within sight of the boiler. Use 14-gauge 

wire in BX cable or conduit properly anchored to the boiler case for mains supply 

and pump circuits. 
Connect a 120 VAC / 15 amp supply to the 

“AC IN” 

tagged leads in the wiring 

box. The max. actual draw (with 5 typical residential size pumps) is less than 4 

amps. 
The 120 VAC power supply to the load pumps (P/V1, P/V2, P/V3, and P/V4) have 

been factory installed and connected to P/V-L and P/V-N for your convenience.  

If you are to use the P/V relay connections for zone valves then the 120 VAC 

connections at P/V-L and P/V-N will have to be removed and properly capped 

off.  24VAC can then be applied using an external transformer to supply power to 

zone valves. The upper 4 pairs of contacts on this green connector strip are then 

powered to manage up to 4 load pumps – the top pair for Load 1, the second pair 

for #2 etc. Once the controller is programmed for the respective loads, the boiler 

will manage all the loads without need of further relays (for loads up to 1/3 HP; 

for more – use a protective relay).
The boiler (primary) pump is connected to the White/Yellow pair labeled 

Primary 

Pump.

 This lead is factory wired to the controller (and its 120 VAC supply) at 

the upper right backside of the controller board – do not attempt to connect the 

primary pump to the Pump/Zone Valve Terminal Block along the controller’s right 

edge - this is for the secondary pumps and/or zone valves only. Connect the 

pump’s Black wire to the Yellow of this pair (switched Hot). The White/ Yellow pair 

should be individually capped if the primary pump does not obtain its power from 

this pair (e.g. if a variable speed primary pump is connected to the mains power).

Pumps can be switched on/off using the touch-screen, so there is no need 

for temporary pump wiring during system filling / air purging. If pumps 

are hard-wired to the panel during the system fill/purge phase, re-wire the 

boiler pump to the Primary Pump leads inside the wiring box so the primary 

pump purge function is active. 

In a new construction application- 

use a construction thermostat – or jumper 

with in-line on/off switch – for on/off management of the boiler. Do not 

just pull power from the unit, or its moisture management routine will be 

interrupted

 (fan turns at ultra low rpm for 90 minutes after burner shutdown). 

Treat it like a computer, where you do not just pull the plug when done. If a “low 

airflow / check vent” error signal shows, check for (and remove) any water in the 

clear vinyl air reference tubes. This has been seen occasionally at construction 

sites where the boiler has been repeatedly de-powered wet. 
The combined current of all pumps connected through the on-board pump relays 

should not exceed 10 amps. The control circuit board is protected using on-board 

field replaceable fuses. Each pump is fused with a separate 5 Amp fuse. The 

Alarm contact is fused with a 5 Amp fuse and the 24VAC boiler control circuit is 

protected with a 2 Amp fuse.

1.8

Removing wiring box covers

Line voltage leads for power supply, 

primary pump and VS output

Line voltage load pump terminals

CAUTION

The internal pump relays are 

protected with 5 Amp fuses.  

The maximum recommended 

load on each fuse is 4 Amps 

(80% of rating).  The maximum 

combined pump load is 10 

Amps.  Isolation relays or 

contactors MUST be used if the 

loads exceed these maximums. 

Содержание SL 30-175

Страница 1: ...tible materials in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Im...

Страница 2: ...ng items 1 x Wall mounting bracket 1 x Condensate trap assembly 1 x 30 psig pressure relief valve 1 x Outdoor temperature sensor 6 x 1 4 x 2 1 2 Lag screws w flat washers WARNING If the information in...

Страница 3: ...e USgpm 25 Minimum boiler flow rate USgpm 6 Maximum operating water pressure psig 30 Minimum water pressure psig 8 Approved installation altitude ASL 0 12 000 Ambient temperature Low F C Ambient tempe...

Страница 4: ...INSTALLATION AND OPERATION INSTRUCTIONS 4 SL 30 175 MODULATING GAS BOILER THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 5: ...NTROLLER 2 1 2 1 GENERAL 2 1 2 2 CONTROL 2 1 2 3 CONTROL INTERFACE 2 1 3 0 STARTUP AND COMMISSIONING 3 1 3 1 LIGHTING AND SHUTTING DOWN THE BOILER 3 1 3 2 PRIOR TO START UP 3 2 3 3 COMMISSIONING 3 2 3...

Страница 6: ...se of neighbouring properties In sealed combustion applications the exhaust outlet should be placed so as to reach 24 minimum above the down turned intake to avoid exhaust re ingestion For sidewall ve...

Страница 7: ...a great degree of installation flexibility Figure 1 shows outer case dimensions and piping and electrical holes Use this diagram to find a suitable location for the boiler See also Section 1 3 Locati...

Страница 8: ...e is not adjacent to a clothes dryer exhaust terminal Avoid agricultural applications where the boiler and or the intake air source are affected by ammonia and or dust Locate the boiler where water le...

Страница 9: ...experienced at the exhaust terminal of a condensing boiler Generally intake and exhaust pipes should terminate at a rooftop or sterile wall location to maximize customer satisfaction Keep exhaust plum...

Страница 10: ...s shall be followed with each appliance remaining connected to the common venting system placed in operation while the other appliances remaining connected to the common venting system are not in oper...

Страница 11: ...sed Permitted PPs materials comprise Single Wall Rigid pipe and fittings and Flexible Ensure compliance with exhaust temperature limitations for the respective materials which typically are ULC S636 C...

Страница 12: ...example can be sited up to 200 equivalent feet from the vent termination using 3 The actual vent travel allowance is reduced for fittings in accordance with Table 3 e g for the SL 30 175 boiler using...

Страница 13: ...onents For PPs connections shall be secured using approved retainer clips supplied by the respective PPs manufacturer All vent connections must be liquid and pressure tight Prior to firing the boiler...

Страница 14: ...common venting system Roof Top Concentric Termination Kits are approved for use with this boiler model The installation of the vertical roof top concentric termination must follow the installation ins...

Страница 15: ...ace the 2 groups of pipes at least 3 apart the closest intake and exhaust pipes shall be 36 or more apart Use same 24 minimum vertical separation Alternately as long as the boilers are identical model...

Страница 16: ...e line extended above meter regulator assembly 3 0 91m within a height of 15 4 6m above the meter regulator Clearance to service regulator vent outlet 3 0 91m Clearance to non mechanical air supply in...

Страница 17: ...inishes or components or infiltrate building envelopes including adjacent structures 1 4 7 Direct Vent Combustion Air Intake Piping There are two basic methods of supplying combustion air to an IBC bo...

Страница 18: ...by transfer of unused intake allowance Combustion air piping if used is inserted directly into the 3 female stainless steel fitting on the top right side of the boiler and run horizontally or vertical...

Страница 19: ...ter may be installed IBC supplied air intake filters have a known pressure drop and fouling factor and should be used as a component of the combustion air system according to the allowable intake leng...

Страница 20: ...ssion Nut E remove Drain Hose G from Trap Drain Outlet F Place Vacuum breaker cap J over the Vacuum breaker opening and push firmly home Remove Upper Compression Nut and Washer C and slide over Boiler...

Страница 21: ...in the installation instructions above 1 5 4 Further installation details Condensate drain must be piped to within 1 of a drain or be connected to a condensate pump Drainage line must slope down to t...

Страница 22: ...AUTION When a condensate neutralization package is installed the pH of the condensate discharge must be measured on a regular schedule to ensure the neutralizing agent is active and effective Figure 1...

Страница 23: ...4 NPT is supplied for field installation at one of the locations shown in the following illustrations Relief valve discharge piping must terminate between 6 15cm and 12 30cm above the floor or per loc...

Страница 24: ...ur from any component in the system An additional benefit is that backflow prevention devices are not required when using these devices Do not place any water connections overhead the boiler leaks can...

Страница 25: ...water volume Default software values will run the boiler s primary pump for up to 5 minutes 300 seconds after burner shutdown Secondary pumps can be set to run up to 5 minutes after burner shutdown f...

Страница 26: ...sful installation There are many necessary components not shown and details such as thermal traps are left out so the drawings have greater clarity We require that our boilers be installed by licensed...

Страница 27: ...1 21 INSTALLATION SL 30 175 MODULATING GAS BOILER Figure 25 Basic Primary Secondary piping with hydraulic separator concept Figure 26 Primary Secondary with Indirect Domestic Hot Water...

Страница 28: ...potentially lengthen the duration of the transition from hot to cool loads SL modulating series boilers can be connected directly to a floor of non oxygen barrier polybutylene material PB tubing For...

Страница 29: ...ing appropriate means such as a manual mixing valve or an aquastat set to130 F for example wired to the boiler s auxiliary interlocks PARALLEL LOAD PIPING BENEFITS AND INSTALLATION RULES Compared with...

Страница 30: ...rated below This approach provides constant head and flow at each boiler regardless of flow variations in the main building loop Each boiler will control its own pump turning it off or on when heat is...

Страница 31: ...ure prior to reconnecting The boiler and its gas piping shall be leak tested before being placed into operation The gas valve is provided with pressure taps to measure gas pressure upstream supply pre...

Страница 32: ...he Pump Zone Valve Terminal Block along the controller s right edge this is for the secondary pumps and or zone valves only Connect the pump s Black wire to the Yellow of this pair switched Hot The Wh...

Страница 33: ...nd switches for each radiant floor zone to present a common thermostat signal to the controller Ensure there are no disturbing influences on the call for heat lines e g no coils to switch an air handl...

Страница 34: ...stat is not applicable with the SL modulating series boilers In the case of a single temperature heat load where zone valves are used to manage individual thermostatically controlled zones each room t...

Страница 35: ...iguration back up and cloning using SD card or USB stick Superior warning messages while setting up the control Advanced Error messages with visual display on the Home Screen Internet LAN connectivity...

Страница 36: ...arder surrounding the active area At the bottom of the display there is space reserved for the boiler status bar Prior to any interaction with the touch screen the display will be showing the Home scr...

Страница 37: ...3 1 STARTUP AND COMMISSIONING SL 30 175 MODULATING GAS BOILER STARTUP AND COMMISSIONING 3 0 3 1 LIGHTING AND SHUTTING DOWN THE BOILER clockwise open close...

Страница 38: ...ately outside the boiler case Ensure boiler has shut off and the appropriate Error information is displayed on the Touch Screen To restart boiler reset power or press Clear Errors in the Advanced Diag...

Страница 39: ...Check and adjust if necessary the high fire CO2 levels first before checking and adjusting the low fire settings High Fire to increase the CO2 turn the adjustment screw Counter Clockwise see Table 7 b...

Страница 40: ...refully 3 The gas supply shall be shut off prior to disconnecting the electrical power and before proceeding with the conversion Ensure that the gas supply is turned off at the gas shut off valve 4 Us...

Страница 41: ...2 Carefully remove the refractory and place in a clean dry area 13 If burner needs to be removed gradually loosen up the 3 screws that secure the burner to the heat exchanger lid using a 2 Phillips sc...

Страница 42: ...INSTALLATION AND OPERATION INSTRUCTIONS 3 6 SL 30 175 MODULATING GAS BOILER PAGE INTENTIONALLY LEFT BLANK...

Страница 43: ...essed air Evaluate the magnitude of clearing required and establish a reasonable burner inspection schedule Some boiler locations may call for annual service others showing clean burners will only nee...

Страница 44: ...der replacement of expansion tank Check also for noise at high fire which may signal water quality problems Check water piping for damage or leaks and repair as needed Water chemistry shall be of a qu...

Страница 45: ...e replaced It is highly recommended that a system pressurization unit such as an Axiom Industries model MF200 be employed to refill and pressurize your system Capture the discharged fluid in a contain...

Страница 46: ...Gas inlet connection on side Gas valve Gas supply line Ignition wire boot Fan housing Fan pressure sensor Fan motor Ignition module Sight glass burner observation port GEOGRAPHY COMPONENTS 4 2 NOTE V...

Страница 47: ...h Vent temperature sensor bracket Inlet return water temperature sensor Removing vent stack test port plug Water pressure sensor Water temperature high limit switch Combustion air intake riser Removin...

Страница 48: ...re one unit and must not be separated The gas valve can be removed from the fan venturi assembly by removing the three T25 Torks screws Take care not to misplace or damage the gasket between the gas v...

Страница 49: ...se with troubleshooting including Electrical Wiring Diagrams Sequence of Operations Flowchart Boiler Component Layout Diagrams PRELIMINARY CHECKS The first step in troubleshooting this system should b...

Страница 50: ...he wire leads by disconnecting their respective Molex connectors Place multi meter probes into sensor s female Molex connector socket Do not apply voltage to the sensor damage may result TEMPERATURE R...

Страница 51: ...the advanced diagnostics section of the controller In general the Fan Pressure and the Required Pressure should be very close to each other while the boiler is in operation If the required pressure is...

Страница 52: ...gnite After 3 Attempts the Capable Controls module provides a single flash at the start of each Purge and Interpurge cycle continuous rapid flashes during the 4 second spark interval solid illuminatio...

Страница 53: ...O MODULE Before resetting the LWCO module ensure that the system if fully charged with water and that all the air has been bled To reset the LWCO module press the reset button The red LED will illumin...

Страница 54: ...e purge Fan Pressure FP should move close to Required Pressure RP if FP is not within 30 of RP and getting closer then check for actual vent system blockage a disconnect intake within boiler case b op...

Страница 55: ...t the end of the ignition trial Improperly grounded pressure vessel burner or unserviceable ignition lead or spark module Ensure pressure vessel is grounded Check the igniter probe flame sensor is ele...

Страница 56: ...2 Ignition Problems SYMPTOM DIAGNOSIS REMEDY NOISY SPARK WHEN IGNITING Ignition lead is not firmly connected Reconnect ignition lead Contaminants moisture on igniter probe flame sensor Ensure probe i...

Страница 57: ...mmeter Air in system or marginal water flow Bleed purge system as required Confirm adequate pump size and temp rise in HX Slow combustion air blower Check that CO2 level is within specification Dirty...

Страница 58: ...mixing Check CO2 level Defective thermostat Refer to manufacturer s instructions Obstruction in condensate drain Inspect and clean condensate drain Unit cycling on operating safety controls Check ope...

Страница 59: ...relay or install a properly sized resistor consult the thermostat manufacturer first then IBC for instructions ERROR WATER HIGH LIMIT LOW WATER CUT OFF WON T CLEAR Boiler is in 1 hour safety lockout R...

Страница 60: ...INSTALLATION AND OPERATION INSTRUCTIONS 5 12 SL 30 175 MODULATING GAS BOILER THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 61: ...6 1 DIAGRAMS SL 30 175 MODULATING GAS BOILER 6 0 DIAGRAMS 6 1 PARTS DIAGRAMS 6 2 WIRING DIAGRAMS 6 3 SEQUENCE OF OPERATION...

Страница 62: ...INSTALLATION AND OPERATION INSTRUCTIONS 6 2 SL 30 175 MODULATING GAS BOILER Diagram 6 1 4 SL 30 175 Boiler assembly parts SL 30 175 Modulating Boiler Parts assembly 6 1 PARTS DIAGRAMS...

Страница 63: ...H 1 200 500 044 V10 0 CONTROL MODULE 1 210 250 488 CONTROLLER TERMINAL BLOCK COVER 1 220 500 021 DOOR ASSEMBLY 1 230 240 006 PRESSURE SENSOR RETURN WATER 1 240 250 258 RETURN WATER PIPE 1 250 240 009...

Страница 64: ...INSTALLATION AND OPERATION INSTRUCTIONS 6 4 SL 30 175 MODULATING GAS BOILER Diagram 6 2 1 Ladder wiring diagram 6 2 WIRING DIAGRAMS...

Страница 65: ...hite black black Vent High Limit Switch Upper Vessel High Limit Switch Water High Limit Switch white yellow black yellow red white red white white white white white black yellow yellow black black bla...

Страница 66: ...INSTALLATION AND OPERATION INSTRUCTIONS 6 6 SL 30 175 MODULATING GAS BOILER 6 3 SEQUENCE OF OPERATION Diagram 6 3 Sequence of operation diagram...

Страница 67: ...g Instructions Leak testing completed gas piping venting system Fan and combustion components System Cleaned and Flushed type of cleaner used ________________________________________________ System Fi...

Страница 68: ...uration Load 2 _____________________________________________________________________________________________ Load Definition Load 3 ____________________________________________________________________...

Страница 69: ...SERVICE RECORD DATE LICENSED CONTRACTOR DESCRIPTION OF WORK DONE...

Страница 70: ...NOTES...

Страница 71: ...E FOLLOWING CONDITIONS IS TRUE An external energy management system is installed that reduces the boiler water temperature as the heating load decreases This boiler is not used for any space heating T...

Страница 72: ...REVISION HISTORY R1 SEPTEMBER 2014 Addition of V10 0 Touch Screen Controller...

Страница 73: ......

Страница 74: ...IBC Technologies Inc 1445 Charles Street Vancouver BC Canada V5L 2S7 Tel 604 877 0277 Fax 604 877 0295 www ibcboiler com 120 213E A R1 September 2014 IBC Technologies Inc 2014...

Отзывы: